how to caculate no load loss, load losses & impedance
percentage in power or distribution transformers
Answer Posted / k.prakashchandra
Short the LV side ,increase voltage on HV ,till you get the rared current. The percentage of this voltage against rated voltage is % impedance . if you connect a watt meter you get copper losses . With open circuit apply rated voltage ,to measure the iron losses with a watt meter .
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is the purpose of using filters in a protective relaying scheme?
how single phase preventer works ?
How time response of the system is divided?
if you are in a software company,then why do you want to come in a core company like sail, ntpc(where lots of trouble like tension but you have a good life in a it company) ?
there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit
What is q factor?
Explain the laying procedure and laying depth of submarine/subsea power cable for 220/400KV system? Also available cable diameter?
if a.c supply is given to the motor,, what happen?
I am B.E.electrical engineer having 7 years of experience in Transformer testing upto 315 MVA.I want to khow how I can get the 'Electrical Valuer' License.
Explain the purpose of inductor in an electric circuit?
State and define ohm’s law?
sir iam from electrical and electronics branch ,can i appear for the hpcl offline requirtment? if yes please mail me on vikram_raju25@yahoo.co.in
what are the things that can cause a three phase motor to crawl?
What is the physical significant of power factor?
What will be the impact on motor performance if a LT motor is rewound with changed motor winding data as given below:- Original winding data: total 04 wires = 02 wires of 17 SWG + 02 wires of 16.5 SWG. Changed Winding data: total 03 wires of 15.5 SWG wire size Motor rating: 160KW, 740RPM, 415V, ID FAN application. Normal Running Current = 95% of FL Current.