how we calculate the 30 KW 3phase electric motor current on
noload
Answer Posted / vikram
P = 30 kw
V= 415
I = ?
PF =0.8
p= 1.732 VI PF
I = 30000/1.732*415*0.8
I= 52.17 Amp (Full load current)
No load current will be 30% of FL current
N.L Current = 30% * 52.17
NLC = 15.65 A (Without taking Efficiency of motor into account)
| Is This Answer Correct ? | 43 Yes | 2 No |
Post New Answer View All Answers
in wind mill use 2100 kw asychronous generator ( induction generator ) rotor voltage : 3300,stator voltage : 690, rpm : 1511 type : MRL063E04 ' we check rotor resistance magger value found following. R-EARTH - 00 M.OHM,Y-EARTH-34 M.OHM,B-EARTH- 33M.OHM R-Y: 31 M.OHM, Y-B: 00 M.OHM,B-R :33 M.OHM HOW CAN I TAKE DECISION?pls ans. quickly
Why electrical power generation and transmission done in 3 phase system not more than 3 phase ?
Why squirrel cage motor can only use with low starting loads ?
what are all the components required to assemble solar panel other than pv cell?
what is effect of leading power facter on the system and billing
what is the best method of grounding in 30 MW generator?
how circuit breaker work.. what is the operations taking place inside a circuit breaker when an overcurrent occurs... is it similar to fuse?
internally connection of photvoltic module
What is miller crystal oscillator? Explain its operation?
On what cycle does thermal power plant operate?
What is the purpose of using busbar mounting fuse?
How to set a Zone 1 distance relay for distribution feeder?
what is your majour contributions in your present job
What is the fault or needs to be done when frequency in ac drives is not changing?
why wire sizes are 3/29 or 7/29 and why not wire sizes are 2/29 or 6/29?