Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is 100%
protection of
generator? Why
95% protection
is used not 100%?

Answer Posted / aswin joseph

95% stator earth fault protection uses an overvoltage relay at the neutral transformer of a generator. Because there is always a minimum voltage at the neutral because of harmonics and zero sequence, a little margin is necessary and only 95% of the generator windings can be covered with this method.
100% stator earth fault protection uses current injection at low frequency or minimum third harmonic voltage to detect earth faults. It does not have the limitation at the earth side of the winding, so using this method and the one described for the 95% you can cover 100% of the stator.
Both detect earth faults at generator stator windings when generators neutrals are connected to earth using neutral transformers or reactance, which make neutral currents too small to use overcurrent relays.
Injection method protects 100% stator windings without the need of a 95% relay. It works on its own.
The principle is the following: a signal generator injects voltage pulses in the windings of the machine at a frequency different from the rate frequency of the system or any harmonic (typically 10 Hz to 25 Hz, 87 Hz...). These pulses are transmitted to ground through the winding insulation and back to the signal generator through the earthing resistor.
Together with the signal generator, the relay also measures the current in the signal injected. In normal conditions, total impedance is high and low currents are measured. If there is a phase to earth fault in any phase, impedance to ground decreases and current increases rapidly, indicating the fault.
This method works even with the machine out of service if the relay is connected (careful with this during maintenance).
This system is normally implemented at the generator neutral transformer, but if it is not available (for example, because a resistance or reactance is used instead of a transformer, or the generator is delta connected), voltage transformers can be connected at the generator terminals with the secondary connected in broken delta, since this allows the injection of the same signal to all windings.

Is This Answer Correct ?    32 Yes 7 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

We have a couple of oil tanks at our plant. One of them does not have a lightning arrester installed. My question is it necessary to install an arrestor on every tank or will this particular one be covered by the arrestor installed on the ajdacent tank, Since all the tanks are close to each other. Basically, I want to know that if these arrestors or protection works in a parituclar area of effect or influence. Thanks

2107


what should be the ideal gauge of wire (In sq mm) for different loads in Ampere?

1493


Draw torque - speed curve and load curve of induction motor? mark operating point ?

2117


What is meant by bus bar protection?

1257


we have a rewind motor of 2Hp,2800Rpm, 220Volt AC. how can we choose the running capacitor for this motor, any formula for that?

1975


Give some example of fault limiting devices?

1430


What is the disadvantage in proportional controller?

1194


how to select automotive wire by mathematical equation with given current, vlotage and resistance

2400


how is the cable tray designed & how its total length is calculated for an Industrial plant Say for Ex. (500KW Motor Load)

1941


What is oscillator circuit?

1188


for compensate 315mh inductance ,how many capaciance required?

2124


i am gng to visa interview this july i have 4 backlogs gre 1010,toefl 75,pls give me the tips pls pls

2209


what is strip power factor?

2226


HOW WE CAN REDUCE THE CIRCUIT COMPLEX OF STAR-DELTA STARTER .BECAUSE NOW WE USING ONE TIMER RELAY & THREE CONTACTOR FOR MAIN,STAR & DELTA ?IF ANY IDEAS PLZ POST.THANK U

2548


What will be result if we connect LT votage to the terminal of HT motor?

2190