Hi frnds :)
plz tell me that i have 100 KVA 3 phase generator so by
thumb rule 100*1.4 = 144 amps
and generaly we can operate at 80% load...so it will 144*0.8
=112 amps....
so now i m confused about single phase load.....if we use
that generator only for single phase the that 112 amps is
total single phase load or i can give 112 amps at red 112
amps at yellow and 112 amps at blue....
i mean that total single phase load that 100 KVA generator
will take is 112+112+112=336 amp ??
Answer Posted / k.prakashchandra
Current in each phase 112 A ,ph voltage say 230 V. Then
apparent power in each phase is about 26 KVA .Sum = 78 KVA
which is almost the permissible load on the gen. If you add
phase currents ,the resultant is zero as they are vector
quantities . You can have a load of 112A in each phase .
| Is This Answer Correct ? | 0 Yes | 3 No |
Post New Answer View All Answers
The electromagnetic torque developed is proportional to what in a D.C series motor?
how to calculate
Anyone who can recommend an equivalent to Envirotemp FR3 of Cooper?
what is difference between speed mode and torque mode in motor?? explain in simple words please.
What are the causes of having an rmu explode after installation? And how do u treat the bushings of an rmu?
Is there any Electrical supervisor license which gives permit to work whole India rather than individual state??
What is the polarization index value ? (Pi value)and simple definition of polarization index ?
sir plz send some previous year questions of jspl.
How to select cable the size, what is the parameters use and what is the formulas use for this cable size calculation?
What are the electrical engineer roles and responsibilities in chemical plant?
what is value of Jin transformer
what is a composite error in current transformers, why occurs & in which it will occur i.e, either metering ct/ protection ct
What does the term supermesh means?
how can tell us the AC indoor or outdoor which Tr and formulls
What is resistance of 50meters, 16sq.mm, single core copper cable?