Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have a question, I visit 01 site and face a problem,
there is 2.5 ton Air Con working, when air con compressor
is running at that time rectifier voltages are increasing
upto 290-295 v and rectifier is giving main high alarm
(rectifier is APC single phase, before starting compressor
rectifier voltages was 230v. when air con is going off
rectifier voltages are decreasing smoothly at its actual
voltages 230v.

Load on Genset phases is this: Red-13.5 amp AC (Air Con
load), Yellow-1.7 amp AC (BTS lights etc.) and Blew-4 amp
AC (telecom system load),
Genset phase to phase and neutral to phase voltages are
also ok.


These are 10 sites having same system and same rectifier
APC brand at every site 02 genset are working but the
problem is same at all these 10 sites.

What will be the reason behind???

Answer Posted / k.prakashchandra

Neutral- shift due to load

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

List the advantages of star-delta starter with induction motor?

1010


Give idea about General Engineering. From which book i can study this topic. Pl. reply me via email. My email is ravi@bhelhwr.co.in, also give the name of book/website, from where i can prepare it.

2055


we have two generators different capacity on 15 MW and other 6MW at 11 KV , 15 MW gen. bus short level current 40KA,and 6MW short level current 25KA,, length of cable 100MTR between 6 MW from 15MW gen. for bus coupling . kindly tell any one can we use both NGR OR one NGR from any GEN. BOTH NGR has diff. rating. Tariq pakistan

1679


Which type of motor is used in trains, what is the rating of supply used explain working principal?

1292


in single phase converter, the no.of scr's conducting during overlap a)1 b)2 c)3 d)4

2070


what is the difference between oil surge relay and buchholz relay.

7038


why Lightening Arrester Probe sharp at Top of telecom tower.

1556


difference bewteen reverse current and alternating current

2226


hello friends.. I have a doubt regarding the operation of dc machines.. I studied in a text book that a dc machine can be used as a generator and as a motor.. is this possible? If so,please send me the info about this topic.. you can also send your info to my mail.

2056


how synchronous condenser is used in place of synchronous generator with out negotiating IEEE standards? Can i use 3 generators as synchronous generators and 2 generators as a synchronous condensers in an IEEE 14 bus system with out disturbing the standards?

2126


132/6.6πš”πšŸ πšπš›πšŠπš—πšœπšπš˜πš›πš–πšŽπš› πš—πšŽπšžπšπš›πšŠπš• πš‘πšŠπšœ πš˜πš—πšŽ πšŽπšŠπš›πšπš‘ πš™πš’πš πšπšŽπšπš’πšŒπšŠπšπšŽπš. 𝙸'𝚟𝚎 πšŠπš—πš˜πšπš‘πšŽπš› πšπš›πšŠπš—πšœπšπš˜πš›πš–πšŽπš› 𝚘𝚏 6.6πš”πšŸ/415𝚟 πšŒπšŠπš— 𝙸 πšŒπš˜πš—πš—πšŽπšŒπš πš—πšŽπšžπšπš›πšŠπš• 𝚝𝚘 πšœπšŠπš–πšŽ πšŽπšŠπš›πšπš‘ πš™πš’πš 𝚊𝚜 𝚘𝚏 13/6.πš”πšŸ πšπš›πšŠπš—πšœπšπš˜πš›πš–πšŽπš›?? π™Έπš π™½πš˜.. πšƒπš‘πšŽπš— πš πš‘πš’??

981


what does vector group Dyn11 tell us? also tell me how will u differentiate between phase lead and phase lag thru this vector group

2081


transformer phasor diagram under load explain it?

2190


How to Prepare preventive maintenance shedule of machine tool.

2021


can anyone send me some sample question regarding power grid corp

2208