DG B-check,C-Check,D-check is depending upon the running
hrs.If the running hrs is not reached as mentioned.How to
conduct the DG checks.
Answer Posted / rajakumar k j
this check is preventive maintainance of DG sets(1000-1500KVA).
1) A-check is done on daily basis here we check:
a) oil level
b) coolant level
c) gauge valve level
d) check for any leakage.
e) cleanliness of DG set.
2) B-check(done after 300hrs of cycle or 6 months whichever is earlier. )
a) check lube oil filter
b) fuel filter
c) air filter
d) bypass filter
3) C-check(done after 1500hrs of cycle or 3yrs whichever is earlier.)
a) all steps of b-check.
b) check/change of air filter (if needed).
c) check/change of other filters mentioned in b-check.
d) change of gaskit of chambers.
4) D-check
a) done in 6000 hrs of cycle.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
How to design the earth grid for lightning protection in an industry
where is the need for short circuit test for 3 see is required and why? can you explain in brief with application
What will be electrical cost per sqft for IT building (basebuild and fitout)and for residential township?
How to check the LM324 Ic
How to assume answer to electrical questions
what is meaning of 230volts ac 50hzs ac supply is it rms or maximum to getting ac 230v what amount of max voltage they will send
what is the cause of voltage dipp or swell in the transmission lines?
What is advantages of VSCF wind electrical system?
in ring main system we use the isolater b/w transfer bus and main bus if we r not use isolatar than wat will be the effect in our sys.
What is earth system using on the floater TN-S or TT. Iam not sure and what ICCP
what is sevice settings for mccb?How can be it setted?
Why a tesa lamp is glow between two phase?
Can i use the B-curve MCB instead of C-curve MCB
What are the difference between normal application Transformer and Solar application Transformer?
there are cam operated switches - why we call cam operated , What is cam ?