why transformer impedance measure in % (percentage)
Answer Posted / 7anoter4
Usually group of transformers presents the same short-
circuit reactance in %
For instance, for S[ rated power] up to 2500 [to 3000] kVA
the percent reactance will be vk%=4-8. Ohmically calculated
reactance will be V^2/S*vk%/100 [ V=rated voltage].
For V=10 kV and vk%=6 for S=500 kVA Xk=10^2/0.5*6/100=12
ohm
For V=6 kV and vk%=6 for S=3000 kVA Xk=6^2/3*6/100=0.72 ohm
As one could see it is more convenient to consider only
vk% instead of ohmic reactance
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
what are the necessary basic electrical topics to learn for mechanical engineer to deal practical problems.
what is the formula for computing cable tray size & capacity
What is the high series capacitance winding on high voltage power transformer ?
who many types of fire explane with exmple
What are differences between Voltage, EMF & Potential difference ?
In ACS 1000 drive we are using 12 pulse converter,why don't use 3 pulse converter.
How do u analyse protection fault when vcb tripping on load
What is open delta Xformer? It's adavntages & Use?
i am studying in final year can i allowed for 23rd UES of Indian army
Is any generator is developed which is operated with out diesal or other expensive source?
Why use in ht motore
full form of electrical?
hi Is there any possibilities to find out the rotation of a shaft or something else by using electromagnectic waves or by IR rays.If s then can v change the dir., of rotation of the same by remotely?& how? plz dn't any1 say "NO r CAN'T"
Explain the working of any one cutting machine
What is the reason that the humming sound is coming from the induction furnace panel?