This is about the recent problem that we have faced in our
project site.
We have 6/7.5 MVA. 66/11kV three phase star - star power
transformer. The neutral was solidly connected to the
earthing mat. But because of high resistance of earthing
mat (130 ohm on LV and 180 ohm on HV), one day LV side
neutral earthing conductor melted and we had a huge damage.
Can any one plz tell me what might happen when we connect
power transformer neutral to the earthing mat which has
high resistance (>100 ohm ) ?????
Answer Posted / k.prakashchandra
Have you measured IR properly, as the values are very high
?The IR should not exceed 2 ohms for a 66 KV MUSS .I do not
know whether primary neutral is to be earthed in case of
star/star tr.It is stated that LV side IR is 130 ohms ,and
hence the maximum earth fault current will be 50A.For 7.5
MVA tr the rated LV line current is about 400 A and EFR is
likely to be set at 80A.It appears that the earth wire
melted due to continuous earth fault current.If there is
conductor to ground fault at a distance of 100 m from tr
earthing ,there will be a pd of 63.5 V /m along the line
between the fault point and the neutral earth. If anybody
stands barefooted with feet 1 m apart along this line, he is
likely to be electrocuted as the power line does not
trip.Further the ground around the earthing also may be at
nearly phase voltage during earth fault
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Why we use ups battery and dsdb battery in thermal power plant
What is the maximum percentage voltage drop (vd%)for a motor control center
Where can I get CPWD electrical specifications & Shedule of rates? Please help me
The 3 phase 400 hp 440 volt slip ring induction motor do not take one phase amps why ? The motor is running good condition
how flow current in 220 kv line to line
Does magnetomonopoles exists? one maxwell equation strongly suggests no, but how about their existance in plasma?
Installation method of self treated earth electrode.
A 100W electric lamp is supplied from a 115V, 60HZ source. The peak instantaneous power dissipated in the lamp filament is
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
use of choke in APFC panels
what is reactive power?, why its measured in VA ? is it transient behavior of system?
r we are using in gas turbine mark (5) frame (6) (made in india Bhel 1997) Ā
What are the difference between CT/PT operated Meter and RRAMR Meter for HT/LT application?
can u describe the method used for protection of transmission line.
What is magneto on a gas generator. how it functions. its out put is d.c or a.c. how it can be checked for correct functioning