How can we calculate ngr resistance for a generator and
Transformer ?
What type of transformer requires ngr ?
Answer Posted / a s bhandari
Ohmic value of neutral grounding resister for a transformer is calculated as follows:
R = Vph/ I where I - value of fault current to be limited to flow through the neutral path, normally it is 50A for 5 sec.
Based on above, for 6.6 kv star side of a transformer
resister value shall be 76.21ohm.
| Is This Answer Correct ? | 0 Yes | 3 No |
Post New Answer View All Answers
What are the different circuits in thermal power plant?
Where servomechanism is used?
What is phase cross over frequency?
What cmos is and its benefits?
how we findout a ignater is faulty or not?
How to calculate wire length,size & current? ( related to control panel)
how can i get an electrical c-certificate?
What is servo motor? what is its purpose?
how to calculate the lightning arrester conductor @ no of earth pits required
why dc is used in control circuit for mv & hv switchgear instead of ac
what topics we have to concentrate for power grid et.written test.and tell what to read for english synonyms and antonyms.
Which type of motor is used in trains, what is the rating of supply used explain working principal?
my question is how to answer the question "you are from b.tech eee background and why do you want to go for banking
What is the direction of current flow in ct secondary...means if the current is flowing from P1 to P2 then what will be the direction of current flow in ct secondaryw
I have 2500KVA transformer delta/star,13.8KV/380V provided with LV 4000A breaker. Already I have 2300KW motor feeder with a full load 90%. Is it possible to connect another 1600A from that breaker? If so how the calculation is done?