I have AC automatic voltage regulator 15KVA
What output currant?
Answer Posted / muzamil
if voltage regulator is single phage..in think its out put
I=kva*1000/230=65.21 amps...in full load,
if regulator 3 phage...I= kva*1000/415*1.732*pf*eff
=15*1000/415*1.732*.85*.85
=28 Amps.
Is This Answer Correct ? | 7 Yes | 2 No |
Post New Answer View All Answers
What is the ratio of Booster transformer?
star delta starter contorl circuit... drawing..
how test transfomer(3 phase75kva) by megger
Dear all, I'm manikandan I have done by DIPLOMA EEE from 2011 , I have 5 years of experience from Power plant instrumentation field , which one field is give long life & which one field is best ,I confused a lot and also I'm studying AMIE, can I choose which department from Section B examination? pls tell me