A group of machines (wind turbines) connected with 33KV
feeder and each machines are having individual VCB. The 33KV
feeder connected with 110KV/33KV substation. The 33KV feeder
tripped by over current at Substation and fault recorded at
Substation as OC-R&Y phase. Same time the group of machines
VCB tripped by over voltage, the fault recorded voltage was
above 66KV by numerical Under/Over voltage relay. While grid
drop time, this much of voltage hike is possible?
Answer Posted / k.prakashchandra
The load throw-off may result in run-away speed being equal
to twice the normal speed ,hence the voltage may also become
twice. Over voltage relay should be set at not more than
120%.You can employ the AVR so that the voltage does not
increase with the speed.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
define the active power?
What is current & voltage ? Voltage perform at any load without current or not?
What is ST and specify its range of voltage.
why 1.7Uo for HV cable Hi pot test?IE standard why?
11KV AND 22KV NETWORK KW CAPACITY IN RING AND RADIAL?
What is speed mode?
What is rotary phase converter?
What is the name of the winding from which the supply is taken for load connections?
Define active filter?
State and define ohm’s law?
what is conductor copnstant of ab cable
why do we measure VIBRATION in -24vdc and why we adjust gap voltage -9vdc to 10-vdc? i am trying to get this information since 5 years, yet i haven't get reliable answer, i hope i can get from you.
What is the lower limit of break-down voltage of converter transformer.
PLEASE SEND ME NTPC RELATED INFORMATION LIKE WHICH TOPICS HAV MORE SCOPE,BOOKS TO READ,CUT OFF...PLEASE.mail at thiru.1203@gmail.com
1. Why is the speed of shunt motor practically constant? 2. Why dc series motor use to start with heavy loads? 3. advantages & disadvantages of separately excited generator over self excited generator?