Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

We have .ht motor which is 60Hz.we run on 50Hz.so that it's speed reduce
but we had one prob.that motor winding temp increase up to 135 deg.we
want reduce this temp.what to do?we arrange ext.cooling fan but not much
effect.we want reduce this temp. Inhouse without affecting much.cost. also
don't want reWINDING OF MOTOR?

Answer Posted / k.prakashchandra

As you have reduced the speed ,the cooling effect of the
shaft mounted cooling fan is also reduced .Either you have
to reduce the load by about 10% or replace cooling fan .

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

1 hp is equal to how much watt?

1191


howmany electrician should maintain for a 1000 kva used plant... in kerala..

2056


is all the servo motors having brake?please specify which servo motors having brake for stop on position and which are not.

1733


What is the function of RCBO? What are the different sensitivity ratings & each application?

2756


what would happen if reactive power (kvar)is increased (more)or decreased (less)? how much exact reactive power should be maintained? and what should be done for that

2215


how much maximum load a 2 core (Single phase) 16mm aluminium wire can take ?

2584


WITCH CARDS IN USE IN FIRE CONTROL PANEL.

1862


WRITEDOWN FEW RELY CODES

2212


derive DC RMS value for half wave rectifier?

3146


What do you mean by lighting transformer?

990


if a 3phase 100kva distribution transformer , 400 v,50 hz, 4-wire system is loaded at 160 k.w mostly 1-phase Lighting & Airconditioning split a.c load what will be the net effect on the power system in terms of voltage, powerfactor, current , efficiency of xformer

1842


I need to connect a synchronous generator to the grid using automatic synchronization and two circuit breakers (one for synchronization, one for end connection to the grid), how to determinate the required diameter of the cables?

2157


How to calculate multiplication factor in kva example 500kva ans pls ?

1875


how harmonics generated in induction furnance? how minimise it?

1952


How does the phase sequence controller works, how it identifies the phases? confirm working principle

2042