How can we calculate ngr resistance for a generator and
Transformer ?
What type of transformer requires ngr ?
Answer Posted / ravi kumar purohit
DESIGN AND SELECTION CRITERIA OF
NGR
Neutral Grounding Resistor:
The power transformer secondary 6.6kV neutral shall be
medium resistance earthed in order to limit the 6.6kV
system earth faults to low values such as to limit
excessive damage to 6.6kV equipments.
Also that the earth faults are not too low value to cause
earth fault relay non-operation.
System voltage = 6.6kV
System voltage per phase = 6.6/√3
Vph = 3810.6Volts
Earth fault current (I) =50A for 5 sec
NGR calculation is done on the basis of following formula,
Vph= I X R
R= Vph / I
R= 3810.6/50
Resistance= 76.21 Ohms
NGR Selected is 6.6kV , 50A, 76.2Ohms, 5sec.
Normally 50 A
| Is This Answer Correct ? | 21 Yes | 3 No |
Post New Answer View All Answers
What is slope...? Explain slope 1 and slope 2...?
When is lag lead compensator is required?
How much of the total hydro power potential has been exploited so far in india?
what is mean by descripiency relay? & wht is its ansi code?
why ups rating in kva? and why ups are in parellel?.why isolation transformer is used in ups?
HOW WORK HEAT PLATE EXCHANGER
why we use 630mm single core cable for transformer secondary side and why two neutral cable
Control wiring of a dol starter for forward and backward
Please brief working principle & construction of permanent magnet AC Servo motor
what type questions asked in hp cl
how r charge carriers produced
how to calculate the loss tangent of electrical cables
bsec exam syllabus (mis)
HOW TO CALCULATE ELECTRICAL, MECHANICAL,& OVERALL EFICIENCY OF GAS ENGINE POWER PLANT
what is upper impedance and lower impedance of a distance relay