11KW Delta motor is taking about 44Amps in star and goes
upto 70Amps in delta and trips OFF. The rated current is
26Amps. Application is for the blower. The motor takes ( no
load without coupling impller ) only 2.5A and 5Amps in star
& delta starter test.Need to know why its taking high
current.
Answer Posted / tj
Following is the check seq. :
1 Check for correct DOR/Phase Seq, ensure termination is
correct n tight.
2 Check the relay for malfunction & its type if it is
thermal then increase setting a bit more than ratd amps &
chk, n if its micro proc based then adjust the setting
acording to motor starting curve.
3 Ensure that suction damper is at min. before starting.
4 Ensure the motor is correct according to fan torque.
5 Check for any abnormal sound or play from fan side.
6 Also check the cable, it should not be underrated, causing
higher potential drop at startup.
Hope the above helps you........
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
WHAT IS THE FUNCTION OF SHORT CIRCUIT MAINTENANCE CT
How to test the vector group of a Yd11 transformer? what are the relations to be checked between various vectors to confirm this vector group?
harmonics filter
Q: How to calculate Transformer losses , tell us by Formula.
Why is back emf used for a DC motor? Highlight its significance.
How can maintain our H.T. motors used in cement plant. please send me procedure.
what is the difference between linear choke and suction choke?
how we can find of current direction(supply comming/out going direction) when a transmission line passing through sides.
IN 1000kva transformer where the oil and winding temperature sensors is connected
WHICH SIZE A.B.CABLE IS USED FOR 11KV.
1. What is maximum permissible distance between smoke detectors ? 2. How do we decide number of smoke detectors required in a large office, warehouse, hall etc ? 3. What should be maximum height of smoke detectors ? 4. Where do we use heat detector, optical smoke detector, temperature sensitive detector ?
What is inrush current?
is there any lightning by passer is arranged in ship like buildings?
Why LED light has advantage of rapid reflection ,although other lights alse reflect.? and this light is considered to be best for transmission usage in case of Free optics
How to know the Max. current caring capacity of the cable by its size ?