how we calculate the 30 KW 3phase electric motor current on
noload
Answer Posted / marcin
Equation with power factor in is the most correct. Several
issues shall be counted before estimating no load current :
- number of the poles
- power factor - there is a curve from the manufacturer
showing how this is changed in a function of power
- size of the machine
- speed
- way of feeding machine - DOL / inverter
Example :
500kW machine 690V 750rpm In=670A, No load - 285A (~42%)
500kW machine 690V 100rpm In=520A, No load - 180A (~34%)
Answer :
KW = 1.732 * V * I * cos phi * K
where K is a factor taking all other circumstances (0,7 to 1
where 1 is ideal situation) lower K for higher number of
poles, multispeed machines, specific construction etc...
Is This Answer Correct ? | 6 Yes | 4 No |
Post New Answer View All Answers
define hysteresis loss, eddy current loss and windage loss
How a band pass filter is constructed?
What happens to voltage when current through the inductor is constant?
What is the requirement of grounding the neutral of single phase generators on load? If the neutral is not grounded, what will be the effect?
what is resver in electrical enginnering with answer
How we calculat the NGR of 3phase Generator, Our generation voltage 11KV
Distinguish between nuclear power station with thermal power station for initial cost, starting period, cleanliness, and transportation of fuel
What happen if we apply square wave or traiangular waveform voltage to the transformer primary winding instead of sinusoidal wave?
What is the maximum number of swithes that can be connected in series up to down stream point in an LV Distribution system?
A system absorbs 100 k J of heat and the increase in its internal energy is 100 kJ; the work done is
I need bhel previous year quetion papers for electrical engineering department.I searched but i could not find out
In power transmission using open belts or horizontal shafts it is preferable to have the slack side of the belt on the top because
what is power factor ? how we can calculate the low power factor and amount of capacitor for improve that low factor ?
Why derivative controller is not used in control systems?
For some transformers we are using solid neutral earthing while some others we are using resistance earthing why ?