Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is the formula to find out the kvar required to
improve the powerfactor from .85 to .99 at 1500kw, 415v.

Answer Posted / alimohmad khatri

KVAR=KVA*SIN(PHI)
KW=KVA*COS(PHI)

HENCE....KVAR/KW=TAN(PHI)

KVAR=KW*TAN(PHI)

NOW, FOR P.F.(1)=COS(PHI(1))=.85 THEN TAN(PHI(1))=.6197
FOR P.F.(2)=COS(PHI(2))=.99 THEN TAN(PHI(2))=.1425

KW=1500 KW IS COMMON FOR BOTH CASE 1 & 2

REQUIRED....
KVAR=KW*[TAN{PHI(1)}-TAN{PHI(2)}]

HENCE KVAR=1500*(0.6197-0.1425)=715.8

YOU NEED TO ARRANGE CAPACITOR BANK OF 715.8 KVAR.

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what does mean of RCT and STR in diffrential CT?

4287


How many double suspension hardware fittings are required on a double circuit transmission tower?

2158


What are the electrical engineer roles and responsibilities in chemical plant?

1740


what is the calculation method to design core and winding of a 200kva 3phase distribution transformer?

2464


What is the basic principle of operation of alternators/dc generators?

1140


HOW TO WORK A VFD?SAY SIMPLE METHOD

4505


Any Electrical Engineering jobs?Please refer for interviews. Thank you

1970


What fomula is used to calculate: 1. rated frequency withstand voltage, and 2. rated lightning impulse withstand voltage.

1768


What is nyquist contour?

1235


what is magnetizing current test in power transformer

2815


Is it a better option to procure screw type air compressor rather than reciprocating air compressor?If so, what is the reason?How should we select an air compressor(100 CFM)? Please mention the important parameters of air compressor.

2006


which is better to use svc or synchronous condenser why ?

1888


what is the star delta connetion and how can do it a three phase motor with control witing with picture

2316


what is size of 3phase 4wire cable to be used for 11 ton ductable A.C and how to calculate cable size for different load

4079


how many safety really of DG sets.

2276