What is the formula to find out the kvar required to
improve the powerfactor from .85 to .99 at 1500kw, 415v.
Answer Posted / alimohmad khatri
KVAR=KVA*SIN(PHI)
KW=KVA*COS(PHI)
HENCE....KVAR/KW=TAN(PHI)
KVAR=KW*TAN(PHI)
NOW, FOR P.F.(1)=COS(PHI(1))=.85 THEN TAN(PHI(1))=.6197
FOR P.F.(2)=COS(PHI(2))=.99 THEN TAN(PHI(2))=.1425
KW=1500 KW IS COMMON FOR BOTH CASE 1 & 2
REQUIRED....
KVAR=KW*[TAN{PHI(1)}-TAN{PHI(2)}]
HENCE KVAR=1500*(0.6197-0.1425)=715.8
YOU NEED TO ARRANGE CAPACITOR BANK OF 715.8 KVAR.
Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
We are planning to synchronized DG's with our captive plant in the event of black start of plant, but before sync we checked voltage of DG with our plant voltage and it varies from 5 V to 450 V. So in this condition how we can sync DG with plant ?
difference between the applicability of nortons and thevenin theorem
What are steps to be taken while designing of DYN11 distribution transformer to achieve magnetising balance?
What is the Surge suppresor? Why using in a UDB's and How it works?
What is cable tray, its type, and its support?
can anybody tell me that for p.f. Improvment we use capacitor banks but how to decide its capacitance. As we all know how to calculate kvar but what abt capacitance value
what is difference between line differential and transformer differential?
aternator every parts and its working
what is the basic construction diffrance between servo motor ans sqiralcage induction motor
can i connect wavetrap in 2 different phase in EHV line?
What do you mean by pull of electromagnet?
pls someone send me sample question papers along with the key.thanks in advance
Why the output of OP-AMP is always less than Vcc?
How to protect sensitive loads such as Dosing pumps inside a factory from voltage surge/voltage fluctuation.
how to find Harmonics and types as per the equipemnts