we have taken HV test of 2.5 k and Megger test on 11 kv HT
cable.here it shows no fault but when we are charging the
same cable with 11 kv supply why the VCB 11 kv gets tripped
can anybody define the possible cause of fault ?
Answer Posted / shariff
The 11kV cable will be designed for morethan 12kV and the
megger applied voltage is just 20% of that rating.. so the
cable insulation might be withstanding at that vg but it is
failing at higher voltage.. So go for the Hi pot test with
DC pulse nearly 15kV...
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
explain the types of drives
what is the working principle of a DG Set, Alternator, & exiter
What are the raitings of Mcb,mccb and Acb in detail ??
How Calculet The UPS AH In Load
while doing high voltage test on 11kv/433 distribution transformer why we only give 28 kv on hv side and 3kv on lv side for power transformers what is the value what factors it depends
how is working bearing heater?
i had aplied Hindustan Petroleum corporation limited for the post of maintenance technician -Electrical,i want model questions,if anybody have please send it or please advice?
how maney type tempereture measurement ?
what is class of SPD and dittels of all class ?
how to select energy meter? have any calculation?
When calculation of fault current and fault Kva is to be done,why always we use per unit value and why we consider the base kva?
What do you mean by cogeneration? What its working principle?
What will be the output voltage of a transformer if it is primarily energized from a square wave voltage source?
What is ignition module of a CAT Gas Genset G-3508 Engine, Alternator SR4B Series. HOw its checked for correct functioning.Is it repiarable or replacable?
Why the earth to phase voltage is high 250 compare to other two phases