Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

we have taken HV test of 2.5 k and Megger test on 11 kv HT
cable.here it shows no fault but when we are charging the
same cable with 11 kv supply why the VCB 11 kv gets tripped
can anybody define the possible cause of fault ?

Answer Posted / shariff

The 11kV cable will be designed for morethan 12kV and the
megger applied voltage is just 20% of that rating.. so the
cable insulation might be withstanding at that vg but it is
failing at higher voltage.. So go for the Hi pot test with
DC pulse nearly 15kV...

Is This Answer Correct ?    4 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why the carbon brushes are broken in srim while the motor runningtime

1641


why fractional pitch winding generally used in alternators?

2899


How are load losses and no-load losses measured at site in a DG set?

1705


what is the constructional difference between a power transformer and potentian transformer?

1707


prove that power consumed in 3 phase delta system is 3 times as compared to 3 phase star system

2163


what is the safety points of vaccum circuit breaker.

2027


What kind of preventive maintenance are there for transformer?

2211


How to calculate Number of Earthing Pits....???

1539


how can calculate resistance box for 15 kw, 6 pole, RV-230, RA-42 motor

3278


What is I to C?

2057


electrical knowelge

1119


why h parameter are called as hybrid parameter?

1917


What is Meter MF if External CT Ratio is 150/1 , PT Ratio is 132/110 Meter CT Ratio is 200/1 & Meter PT Ratio is 110/1

1809


Hello to all, Please someone can send me HPCL ELECTRICAL Engg. Sample papers to me? Its urjent....my email address is.... raviasiapacific@gmail.com

2087


distribution is maximum done by a)radial b)network c) parallel d)b & c

1898