WHY TEMPERATURE TRANSMITTER USED AS WE CAN CONTROL THROUGH THERMOCOUPLE/RTD

Answer Posted / lokesh gatty

We cannot control through thermocouple/RTD, they are only
measuring elements,which is connected to temperature
controller which as set value for which point it has to
control temperature (PID/Relay logic control)..Meanwhile
Temperature transemeter is used to convert mv/ohm to anolog
signal(4--20 ma)...we have to refer ohms/mv to degree Celsius
table

Is This Answer Correct ?    24 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

which processor is used in dcs.

1799


Linear amplifier.

1517


What are the charcterstics of a P&ID controller block for Governor speed raise or lower for a load sharing functionality between 4 Gas turbines in droop mode.

2465


how can i check vortex shedder bar it is ok? if there is ohms condition are shown correct?

1693


whats the abbreviation of IOP? is it instrument of power or input open problem?

638






What are different types of valves?

655


What is the difference between conductive lined pipe and conductive unlined pipe? Why do we see that?

2592


How works weighfeeders in cement industry? what is the working principle?

1497


i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....

967


Programmable Logic control.

1494


Explain pH, Conductivity.

1675


What is stripper & spilitter ? Diffrence in this.?

2045


How to Calibrate Interface Level Troll in field

757


How to convert mmWc(mili meter water colam) to tph(ton per hour)?

461


on interface level transmitter model(RTG3302-EMERSON) What is threshold valve how can we select correct threshold value T1,T2,T3,T4 When interface water & hydro carbon

1671