To find closed tank level by DP transmitter , how to
findout its range.and insomeplace they using range like -
1500 to +1500 mmwc why not 0 to 3000 mmwc. how they spilit
they range for minus and plus.and why?
Answer Posted / yashwant
THIS IS LEVEL MEASUREMENT USING DP TRANSMITTER, CLOSE TANK
MEANS PRESSURIZED ,PRESSURE IS EVERY WHERE IN SIDE TANK WILL
BE SAME. LOW SIDE WILL BE TOP SIDE WHERE ALL CONDENSATE
COLLECTED THIS IS REFERENCE SIDE, NOW ON OTHER HAND HIGH
SIDE WILL BE LOWER, DIFFERENTIAL PRESSURE OBSERVED AT DPT.
LOWER SIDE WILL BE ALWAYS FULL IE FULL SCALE IF YOU ARE
HAVING TANK HEIGHT 1500 MM THEN PRESSURE AT LOWER SIDE IS
1500 MMWC. AND THAT OF HIGHER SIDE WILL BE THE ACTUAL WATER
INSIDE TANK WE SAY 500 MMWC STEAM PRESSURE WILL BE EVERY
WHERE SAME SO NO NEED TO CONSIDER PRESSURE INSIDE THE TANK.
MINUS AND PLUS WILL BE JUST FOR HAVING DIFFERENCE IN TWO
COLUMN IE HP AND LP. ALSO TANK IS NOT PRESSURIZED YOU CAN
USE PRESSURE TRANSMITTER CALIBRATED IN YOUR RANGE (HEIGHT OF
TANK MMWC)
| Is This Answer Correct ? | 6 Yes | 4 No |
Post New Answer View All Answers
How to measure the dust in chimney(spm)?
what is function of switch, and how is it work, explain with difination
WHAT IS THE DIFF. BETWEEN SKIN TEMPERATURE AND PASSES TEMPERATURE..?
How the warning lamp of a charging-system is activated ?
what is o2 analyzer and how it measured ,what is the role of this analyzer in cfbc boiler...
What are the charcterstics of a P&ID controller block for Governor speed raise or lower for a load sharing functionality between 4 Gas turbines in droop mode.
Explain PID controller tuning & any one method used for it.
Pl send the model question paper of mahagenco account officer post
Displace type LT to be calibrated in workshop, wt. 40, dia- 60 mm, density- 0.8kg/cm3.
is there any digitel grevity meter availaible in the market by which we can measure specific gravity of a battery?
If a control valve is hunting means means if we are giving 50% to the cv, the cv will open at 51% then slowly slwoly it will reaches 49% , so what to do for solve this problem. The cv is double acting and mounted for anti surge operation, it having 4 nos. volume booster, one sov, one positioner, etc..?
why micro controller 8051/52's clock frequency is internally divide by 12 ?? and why it is further divide by 32 in UART serial communication ??
what is diffrance between FF & SMART, explain with difination
full process of gas turbin?
dear sir we have insatlled positioner model no.sipart PS2 make Siemens at our control valves . now problem is if we want to increase the response of valve opening speedy /fast. what parameters do we change for positioner ? any idea. please guide us.