How can one improve linearity of an RTD based temperature
measurement system?
Answer Posted / guest
RTD has +/- 0.4% nonlinearity when used over 0 to 200 degC.
This is due to the relationship R= R0*(1+aT+bT^2). The
change in resistance for 0 to 100 degC is 38.5ohms for a
Pt100, while it is lesser at 37.3 ohms fro 100 to 200 degC.
Using a two slope method, one for 0 to 100 deg and another
for 100 to 200 degC, the linearity error can be brought
down from +/- 4% to +/- 0.1%.
Is This Answer Correct ? | 5 Yes | 3 No |
Post New Answer View All Answers
How it the difference between force balance system and dispalacement balance system?
Draw a wheatstone bridge circuit showing supply, meter and 3 wire RTD connection
what is 24vdc live and dry supply
Explain PID, ON/OFF, Controls
how many types of viberation transmitter and how to calibrate and where use of vibration transmitter
what is function of sensor, and how is it work , explain with difination
Q-Explain the different load conditions that will produced different offset which may or may not be acceptable to thhe control function
sir i m preparing for BARC but i am not getting any papers to prepare for this exam so please send me some sample papers to my i.d for the preparation of barc.
few questions on RS 232,1 question on relationship of impedance and turns ratio, many questions on flowmeters
Derive capacitance to 4-20ma conversion formula / relation in capacitance type pressure sensor?
what is the usage of QDV & VOLUME BOOSTER
how can leve transmetter calibate in feild .and also put cv and flow plz .....
How to calibrate the flow transmitter
what is the field bus calble ? what are diffrences in orang colur cable and black coular calble ?
If i have 4 Allen Bradely make RS logix 5000 PLC and for viewing that we are using 4 RS view SCADA for 4 different packages. Now, I will want to view two packages on only one SCADA. Then how i will do it?