Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

11KW Delta motor is taking about 44Amps in star and goes
upto 70Amps in delta and trips OFF. The rated current is
26Amps. Application is for the blower. The motor takes ( no
load without coupling impller ) only 2.5A and 5Amps in star
& delta starter test.Need to know why its taking high
current.

Answer Posted / mohammed raffi

In Blower application, starting current will be more than
normal until it gets full speed due to dampers, hence
better idea to use OLR with starting current delay time and
running current delay time setting. so that while starting
time this OLR waits for some time delay even starting
current is more than normal and trip.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the estimated total hydropower potential of india?

1094


How the over load setting for HT Motors calculated-provided in Numerical Relay

1745


what is x'mer ,isolation x'mer & yltra-isolation x'mer?????

2389


How to calculate the copper in HT motors if KW, RPM & Voltage is given

3155


Mention the disadvantages of low power factor?

1078


how does a submersible pump work..?

1896


what you have to see after one week or month from the day of installation of transformer ?

1664


How we select the vector group of 3phase power transformer?

2645


When is lag lead compensator is required?

1077


what is the saturation point of crgo lamination.

2182


why are the maintaine power factor and how can this control and this is how work.

1924


i have gear oil pump with single phase motor.some time its motor starts running in reverse direction rather than forward direction...whats the reason behind this issue. 1- either capacitor is week? 2- or winding is week?

1342


how we do Vector group ,magnetic balance and tap changer test in Transformer?

2427


what are the stresses in circuit breakers ?

1968


What is the formula of frequency ?

1410