11KW Delta motor is taking about 44Amps in star and goes
upto 70Amps in delta and trips OFF. The rated current is
26Amps. Application is for the blower. The motor takes ( no
load without coupling impller ) only 2.5A and 5Amps in star
& delta starter test.Need to know why its taking high
current.
Answer Posted / mohammed raffi
In Blower application, starting current will be more than
normal until it gets full speed due to dampers, hence
better idea to use OLR with starting current delay time and
running current delay time setting. so that while starting
time this OLR waits for some time delay even starting
current is more than normal and trip.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is the estimated total hydropower potential of india?
How the over load setting for HT Motors calculated-provided in Numerical Relay
what is x'mer ,isolation x'mer & yltra-isolation x'mer?????
How to calculate the copper in HT motors if KW, RPM & Voltage is given
Mention the disadvantages of low power factor?
how does a submersible pump work..?
what you have to see after one week or month from the day of installation of transformer ?
How we select the vector group of 3phase power transformer?
When is lag lead compensator is required?
what is the saturation point of crgo lamination.
why are the maintaine power factor and how can this control and this is how work.
i have gear oil pump with single phase motor.some time its motor starts running in reverse direction rather than forward direction...whats the reason behind this issue. 1- either capacitor is week? 2- or winding is week?
how we do Vector group ,magnetic balance and tap changer test in Transformer?
what are the stresses in circuit breakers ?
What is the formula of frequency ?