what is the safe meggar values for motor, transformer HT, LT
and Cables?
Answer Posted / keith
If you need it to keep working, such as a sewage or storm
water pump,most reputable companys would trend the readings
beginning with the date the started servicing the motor and
watch for a dramatic decrease in test readings. One has to
be aware of the capacitance effect that water has on the
motor cable of a submersible pump as well as understanding
that it is normal to see a gradual decrease over a several
year period from above 200 megaohms @ 500 VOLT d.c. ( brand
new)to eventually down to 10 to 20 mega ohms. I have found
that although motors will run down to 2 mega ohms 230 volt
3 phase and 1 mega ohm to .6 mega ohms 480 3 phase they
don't run much longer. More important is to recognize
dratic decreases between monthly to quarterly readings as
they indicate potential failure ( direct short to ground)
which could trip main distribution breakers, thereby
effecting other motors or equipment by robbing them of
power. i.e. Alarm cicuits that are not battery back up
equipped.
Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
list the type of vfd? wich is sutable for heating kiln?
in indoor type circuit breakers why only the corner breaker trips specially during cold season. What is the reason.
why are the maintaine power factor and how can this control and this is how work.
In diesel generator how AVR get voltage to excitation. And basic diagram DG EXCITATION CIRCUIT.
What is the meaning of floating point earthing in battery backed systems ?
neutral earth resistance testing is it possible for transformer while in load condition
What is the kiosk parts, about them and their functions ? If anybody have some PDFs files or details about this plz send it on tawhidfaisal@Yahoo.com
3- What is the target from Zero Impedance, Single Phase Imp., S/C Imp. and magnetic balance tests?
Wind mill
What conditions are required for transformer to operate at low frequencies ?
how to select the automotive wire size by mathematical calculation. for xenon headlamp with ballast. the ballast given data voltage 10-17v,current permenant 6amp, run up phase is 15amp, peak at swicth on max 400micro sec is 40amp.the sum of cable resistance is 150mohm.please provide referenc document if any for relating the peak at switch on current,time & wire wire size
what is the difference between delta delta and star delta connection transformer? why we use delta delta transformer since it need earthing transformer for grounding?
Sir, My doubt on cable sizing calculation, Load:74 KW calculated cable 1 run 50mm2. Now client asking us to reduce cable size by increasing runs. Sir, My question now when my mind strikes with 2 options 1) Divide load 74/2 = 36 and calculate cable for 36+36 making it 2 runs or 2) Simply i can divide 50mm2 /2 ie. 2 runs of 25mm2 Please suggest me sir
I have a CT meter with ratio 60/5. The meter reading of previous month was 3290.49 and that of current month was 3797.26. How many chargeable units as per normal meter should be my reading.
please send 5yearje solved papers on my email himmatsinghnathawat@gmail.com