how calculation to be done of cable size/o.h. conductor
size of 11kv h.t.for the load of 2175 kw

Answer Posted / k.prakashchandra

The current is about 120 A. But it is not continuous.You
have to the study the list of OH conductors available in the
market.For 120 A and 50' Temp rise ,weasel ' ACSR conductor
is enough. Then you have to consider voltage regulation
which should not exceed 6% and further development. Rabbit
ACSR conductor is the next one with carrying capacity of 148
A for 30' temp rise and 183 A for 50 ' temp rise.Temp rise
is for calculation of maximum sag.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the real function of reverse power relay in generator panel while syncronising?

1594


What do you mean by a phase angel of instrument transformer?

630


How to connect the chemical earthing and complete process tell me plz

1385


Name one of major transformer company in KSA ?

745


The screw thread commonly used for transmission of motion is one of the following types of threads

686






please send the IS strandard for electrical to sakthi_murugan86@yahoo.co.in

1813


How we can recongnise the phase displacement of transformer connection between primary & scondary...plzzz explain it with example.........

1930


why power factor is important?

8281


should %impedance be high or low in a power transformer? if so why?

1477


what percent do you derate your copper wire when you change from copper buss to copper wire

1536


What is the minimum underground tank size capacity considered for firefighting purpose?

1464


we all know voltage is a force(emf), and the force always devides if 2 or more than2 loads are there but why does the voltage remains same is parallel, it must devide na ???

1503


What is installed in PAC that is control the humidity

1046


What is the function of attenuator in cro?

726


how much maximum load a 2 core (Single phase) 16mm aluminium wire can take ?

2178