whycircuit breaker is not connected at the generator end
where the capacity of the generator is more say 60MW, 100MW
etc.
Answer Posted / kunal singh dabi
Due to following points
1)Transient Recovery Voltage (TRV)
2)Higher X/R value
3) Delayed current Zero
circuit breakers was not used after above 60 MW generators.
However please note that now full line of IEEE C37.013
qualified medium-voltage vacuum generator circuit breakers
for voltages up to 24 kV and generators up to 200 MW for
both indoor and outdoor applications are available in
market.
Please note that Circuit breakers applied to generator
switching applications are subject to conditions quite
different than those of a normal distribution circuit
breaker used in industrial, commerical and utility systems.
Distribution circuit breakers, whether of the outdoor
substation type or of the drawout type for use in metal-
clad switchgear, conform to IEEE C37.04 (basis of ratings),
IEEE C37.06 (preferred ratings), IEEE C37.09 (testing) and
IEEE C37.10 (application.)
| Is This Answer Correct ? | 5 Yes | 6 No |
Post New Answer View All Answers
HOW WE CALCULATE CURRENT IF THERE ARE NOT PRESENT ANY AMMETER OR MULTIMMETER??????
what happens if earth of 33kv cable is not connected to earthing pits? please send this query's answer to ngrm.sudha249@gmail.com
what are factors to be consider to design a HT & LT motor?
how much UPS neutral erath leakage current.
how to check three phase motor torque value?
sir please send me previous year questions of jspl of electrical section through which i could prepare myself fpr the test.
why we have and use 3 phase not 2 or 4 or other in power system?
11 kv input, 66 kv input advantages
What is the difference between electronic regulator and ordinary electrical rheostat regulator for fans?
How much pf maintan in dg set in 6o% load,when Dg runnig Neutaal Earthing removed what happen.
Is it advantages of having star-delta vfd than normal star vfd , if yes why?
how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.
what is the working process of over & under voltage relay.
Explain about Dubai electrical sysaem? Explain about Dubai drinking water system? Explain about Dubai Burj tallest building Electrical,Water.etc.. maintenance system?
l&t switch FN 63 handle position can we change