dear all, in motor operation , motor is of 100 hp and
bimetal relay setting is 130 amp, if relay is getting
tripped on 120 amp balance current what can be the
reason? Relay is newly replaced. I dont know but is
there any frequency effect in thit case? Can frequency
variation affect bimetal relay operation?
Answer Posted / k.prakashchandra
Bimetallic relays are not very accurate.Ambient temp also
plays a role for setting as the relay acts at a certain
temp.Hence you have to compensate for ambient
temp.Frequency has no effect on the setting .
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540
how to calculation increase capacitor,increase power factor for three phase.
What is a Phase shift meter? Where can I get one?
how you configure motorvision relay (L&T make)from DCS
Air circuit breaker safety
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
plz send me Bhel, Mahagenco, sbi previous exam paper for electrical engineer on my email-id kambali_smita@yahoo.co.in
If we have use two power cable for incomer, that time how many use cbct for earth leakage protection? 1 or 2 if 1 way? If 2 way?
HOW TO CALCULATE EARTHING SIZING?
what does a k rating in a transformer means?
What should be the amps for a MV fuses for transformer 630kVA 20(10)/0.4 kV
What is safety of Ht panel
I have finish diploma electronics and five years experience in electrical field in ht service how can i get c licensce or other electrical certificate
could you measure current in parallel?
What is the type of earth fault protection used in battery? explain.