why we remove capacitor connection in 3 ph Induction Motor
while taking noload test.

Answer Posted / loboreliance2003

Actually the question should be why is the capacitor bank
connection to be removed from the motor before taking the
no load test. This has nothing to do with capacitor of
motor. 3Ph induction motors dont have capacitors to
start.These are only used for single phase motors.

The answer is that capacitor bank is provided on any
Inductive load due to power factor dipping to below0.8 and
sometimes even to 0.5. To improve the power factor we have
to connect the capacitor banks depending on the size of
motor.

But if motor is not run on load then it is not necessary to
connect the capacitor. Hence no load tests can be done
without having to connect the capacitor bank to the motor.

the other reason is that there is danger of over voltage
due to capcitor being connected then PF will be greater
than 1 which could damage the motor windings. I have faced
these motor burning problems due to this reason.

Is This Answer Correct ?    8 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

magnetizer priciple

1557


An impedance of 100 ohms resistance and an unknown inductance is connected across the capacitor. The resulting impedance is a pure resistance of 500 ohms ifω = 10^5 rad/sec. calculate the values of inductor and capacitor.

703


What is quadrantal symmetry?

1078


how rectifier transformer work in electroststic precipetatore(esp?

2082


How one can check the MAIN of a house wiring ?

1445






what is upper impedance and lower impedance of a distance relay

1575


Can anybody inform me about the pattern of ECIL GET( Graduate Engineers Trainee) interview for Electrical students? Will there be HR round as well? I thought of preparing for 2 to 3 subjects thoroughly. Will it be sufficient? Please share your thoughts.

1694


hello everybody. what does an abnormal stator winding impedance or dc resistance show? thanx

1462


THERMAL CAPACITANCE IS MEASURED IN..................................................

1681


Whats the minimum value for I.R. that can be allowed for HT & LT alternators for operation?

3383


In Electrical 'Single Line Diagram' cable nomenclature shows "2 X 1C X 630sq.mm to be provided for one incomer. The question is how many cable to be proved for one Incomer.

1276


CALCULATE THE TOTAL VOLTAGE DROP AND SELECT THE CABLE SIZE IN MM-SQARE FOR A PANEL-262KW AT 110 METER FROM THE SOURCE SUPPLY , SUPPLY VOLTAGE 240/415

2223


how we can calculate 2 phase welding transformer rating or total power?

1390


how to find out cable size if load is 2800 watts, 230 volts AC supply and load distance is 1800 meters

1077


what is the differencce inn series and cascade connection??

4220