Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

hi can you give any body fault level calculation, generator
fault level calculation,transformer fault level calculation
for system fault level with equation? i have 3.3kv
generation voltage three gas gen sets, one is 1.9MW,2nd is
2.5MW,& 3rd is 3.8MW & i have 11 kv generation voltage one
gas gen sets is 3.8MW, we are step up to 22kv by transformer

Answer Posted / dhiren

Hello Rajeshbhai,

You have not mensioned the capacity & impedance of the
transformer

for example if we have

A 5MVA, 11/22KV transformer with a 5% impedance.

Maximum fault MVA will be

5MVA/0.05 = 100MVA

Is This Answer Correct ?    2 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why does the speed regulating system adopting I controller have no steady-state error? In this single closed-loop speed regulating system, when the input of the I controller Un=0, what is the output voltage of the regulator? What factors do the output voltage depend on?

1917


why the projects getting loss?

1989


hey guys help me out.....what  are the industrial uses/functions of nozzles in industries 

1648


determine two methods to find loose connection in operational electrical system?

1745


In a power conditoining unit (inverter) of a solar plant when we measure the d.c. current fed by different strings of solar plates to inverter, the current in the negative wire is less almost by 1 ampere to the current in its positive wire say current in positive wire 5 A , then current in negative wire of the same string is 4 A. Since the current entering should be equal to current leaving then why the current is noticably less in negative wire.

1656


Can you tell me more about pu systems (per unit systems )calculation in large power systems? how to get the base for voltage and power in generator, transformator and transmission lines?

2344


what are the pecularity of shaver sockets ?

1970


5- What is the task (function) of the excitation and isolation transformers in power plant? 6- What is the task (function) of LCI (A), LCI (B) and LCI (COS) in power plant? : LCI (A) and LCI(B) are load commutating inverter for generator turbine starting. , LCI (COS) is load commutating inverter change over switch

3869


What happens if we connect a single phase energy meter in reverse polarity.

2418


How to calculate energy stored in a capacitance

1225


SIR, GIVE ME OPGW SAG CALCULATION FORMULA I AM DAE ELECTRICAL. THANKS

6954


What is thresh hold value of current?

2246


i have some screw comprressor with 630kw power,i have established them with simple star to delta circuit,by the way there is so much inertia when the screw comprressors start, can you offer me contactors power with 400vac or any cataluge to choose the contactors

1906


what's the simultenous maximum demand (SMD)..what the diffrent MD and SMD?

2621


in HT service 3ph 4 wire service Y-phase voltage shows zero . whether it is meter fault? or what be the reason ? if y-ph voltage zero ,can current is recorded? reasons for failure?

1991