hi can you give any body fault level calculation, generator
fault level calculation,transformer fault level calculation
for system fault level with equation? i have 3.3kv
generation voltage three gas gen sets, one is 1.9MW,2nd is
2.5MW,& 3rd is 3.8MW & i have 11 kv generation voltage one
gas gen sets is 3.8MW, we are step up to 22kv by transformer
Answer Posted / dhiren
Hello Rajeshbhai,
You have not mensioned the capacity & impedance of the
transformer
for example if we have
A 5MVA, 11/22KV transformer with a 5% impedance.
Maximum fault MVA will be
5MVA/0.05 = 100MVA
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
will there be any problem by recovering slip from single phase induction motors?
What is power distribution criteria for converting single phase unbalanced residential load to 3 phase star connected balance system. Does total KW converted to 3 Phase. Means Divided by root 3.
WHY EXCITER PHASE SEQUENCE ARE OPPOSITE THAN STATOR SUPPLY PHASE SEQUENCE IN SYNCHRONOUS MOTOR >
What is the rotor frequency of 10 Hp 1440 RPM 50HZ 415V ?
Transformer diagram mention each parts ?
Why single phase induction motors are not self starting ?
What is formula calculation size cable wire ?
How to know Resistance and Reactance value of main and aux winding of single phase capacitor start capacitor run induction motor to find capacitor value?
What is core CT & it's function?
what are carbondioxide and dcp used in fire extinguishers
Is phenomenon of resonance is harmfull fr the machine? if not or if yes please explain it?
difference between ac series and parallel circuit
What is the maximum No. of out going mccbs permitted from an LV distribution paqnel? What is the ampere relation between incomer and out going switch gears/mccbs?
WHAT IS THE CURRENT CARRYING CAPACITY OF 2.5/3 CORE HI TUFF CABLE,WILL IT SAFLEY CARRY 8.6 AMPS OVER 120 METRES,CAN YOU ALSO ANSWER WITH FORMULA FOR WORKINGS OUT ,THANK YOU 3RDYR APPRENTICE.
How to know vacuum in vacuum cylinder of breaker in working condition