what is the function of anti-pumping in circuit breaker?
Answer Posted / vale
The anti-pumping relay is a device in circuit-breaker whose
function is to prevent multiple breaker closures. For
instance, if the operator gives the closing command to the
breaker by pressing the close button and the breaker
closes. However, a fault in the system causes the breaker
to trip. Since the close command is still in the pressed
condition, there is a chance of the breaker closing again
and being tripped by the relay multiple times. This can
damage the closing mechanism of the breaker. The anti-
pumping relay prevents this by ensuring that the breaker
closes only once for one close command from the control
panel.
| Is This Answer Correct ? | 40 Yes | 6 No |
Post New Answer View All Answers
What is the effect on Power factor and capacitor when your company load is more than 70 % of welding transformer
how to calculate maximum current
I meggared my 2c*70 sq mm AL AR XLPE cable. its one end show 50 M ohm . is my cable is safe for laying. I have only one phase and neutral.
Why Water motor is not taking a load or pressure while everything is correct. (Note: Motor running properly)
explain me the relation between torque, frequency,speed,voltage and current in the 3 phase induction motor?
Which motor is 3.3 or 11kV more reliable, in terms of efficeancy,maintenance, reliability.
why we use sinosidal voltage / current instead of others in system?
it is possible to measurement of tension of slipring induction motor(SRIM)carbon brushes, any maesuring instruments are available in the markets.
What happen when change order of CT in GIS feeder?
What is the working principle of MIG welding? and its out put Voltage?
actually i can't understand what is 3dB ? and it's really not clear to me.please any one let it me be cleared.
If 24 KVA AVR having Input voltage 200-400v, Output voltage 415+-1%, what will be the voltage if Load is 13A.
Explain the purpose of inductor in an electric circuit?
How does a tertiary winding filter harmonic(espcially 3rd one) from entering into load system?
Please tell me the power flow from pmg to main rotor of an alternator (Including AVR unit)?