if voltage is not builed up in small generator what will be
the reason?
Answer Posted / shakir
there are so many reasons:
1.the exciter might have problem
2.the ac produced in exciter is converted into dc before
supplying it to the rotor.the diodes used for this purpose
might have problem.
3.when u start the generator there should be a residual
magnetism to induse the voltage.if u will not use the
generator for long time, it will loose that residual
magnetism.for that purpose u have to give flash over
voltage.
4. the exciter winding might be grounded.
5. the input (D.C.from voltage regulator)voltage to the
exciter is not enough to create flux in the exciter.
6.faulty stator winding
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What types of CMOS memories have you designed? What were their size? Speed? Configuration Process technology?
how to calculate single phase motor efficiency ?
physical identification of HT & LT panel
in electrical control panel. how can i choose the cable rating. (example - 11kw motor, 18-25A mpcb}
I need a formula to calculate the size of cable as per load but in the terms of length. Please Reply me as i search lot of sites but i did not get the answer.
WHAT IS MEANT BY INSULATION CLEARANCE IN VACCUM?
how do u gauge the size of the cable ?for eg. consider a 300 sqmm L.T Cable.How do u determine the size of the cable seeing it pratically?
What is difference between Over Current & Earth Fault protection?
Why the moulded plug comes with domestic appliances instead of assembled plug like anchor, Vinay 5/15 A.
what do you mean by class PS CT and what are technical details needed for calculating it?
what is two point starter?
If rotor works in clock wise what happens
Why water bubbles when D.C. Current is passed through it? Why not when A.C. Current is passed?
what is the difference between circular wdg & ractangular wdg?
Name the test signals used in control system