for a 132/33kv transformer secondary is star and is
connected to NER. and from secondary a cable is running to
33kv swbd. since the cable is single core do i have to run
neutral cable also to 33kv swbd.???
Answer Posted / pichumani
It is not necessary to run a neutral cable as the same is
not requried for a 33 kV 3 wire AC system. But you need to
be cautious about the circulating/eddy current (since in
is a single core cable) which flows through the screen of
the 33kV cable. The voltage genrated by the circulating
current should be more than 130 V as per IEC standards. In
case of heavy circulating current the cable would get
heated up. You may do earthing of the cable only at one end
and leave it open at the other end. In case of a very long
cable with joints in between, mid point bonding is
suggested.
Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
why we use circuit breakers for switching instead of normal switching device?
Please explain, how to test vector group of tranformer(Delta y1) . Thank
how to calculate the formula of cable size if motor kw is given
Why Ac Systems Are Preferred Over Dc Systems?
what material is the electrical housing wire made of? is there any difference for the telephone lines?
In synchronization circuit what is the function of Interposing voltage transformer(IVT)and Reverse voltage transformer(RVT)
Why the frequency of ac in india is 50 hz but in some other countries it is 60 hz.
What is the function of a neutral reactor.
what are the applications of TIG welding
what is diff btw electric,magnetic & eletromagnetic field
How PADO software increase the efficiency of power plant?
why servomotor motor? where i apply for best output?
Power Factor Correction Panel (Manual & Automatic)
Can I use star delta connected induction motor for dual supply voltage?
what is the principle of operation of CFL ??