Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

for a 132/33kv transformer secondary is star and is
connected to NER. and from secondary a cable is running to
33kv swbd. since the cable is single core do i have to run
neutral cable also to 33kv swbd.???

Answer Posted / pichumani

It is not necessary to run a neutral cable as the same is
not requried for a 33 kV 3 wire AC system. But you need to
be cautious about the circulating/eddy current (since in
is a single core cable) which flows through the screen of
the 33kV cable. The voltage genrated by the circulating
current should be more than 130 V as per IEC standards. In
case of heavy circulating current the cable would get
heated up. You may do earthing of the cable only at one end
and leave it open at the other end. In case of a very long
cable with joints in between, mid point bonding is
suggested.

Is This Answer Correct ?    1 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

300m long and 30kw inductive loade 3phase supply how many size cable required

1412


pls someone send me sample question papers along with the key.thanks in advance

2375


What is MS-EXCELL?

2226


How many types of losses occur in a transformer?

1136


what about SAP/MRP regarding manufacturing of electric motors and all drives?

2004


in single phase converter, the no.of scr's conducting during overlap a)1 b)2 c)3 d)4

2049


What types of CMOS memories have you designed? What were their size? Speed? Configuration Process technology?

3666


What tests should i carry over on a newly rewinded DC Generator with voltage rating of 38 volts and current rating of 350 amps, to certify that the machine is OK?

1856


How to calculate that clean water supply in one Day from 150 KLD STP?

1984


what is the excess air in furnace

2028


Why are the laminations insulated from each other?

1140


In Plumbing services What are accessories we consider for a bathroom?

1977


what are symmetrical and non symmetrical components in electrical installation.

2060


How PADO software increase the efficiency of power plant?

6462


how to erect roof control panel?

2026