for a 132/33kv transformer secondary is star and is
connected to NER. and from secondary a cable is running to
33kv swbd. since the cable is single core do i have to run
neutral cable also to 33kv swbd.???
Answer Posted / pichumani
It is not necessary to run a neutral cable as the same is
not requried for a 33 kV 3 wire AC system. But you need to
be cautious about the circulating/eddy current (since in
is a single core cable) which flows through the screen of
the 33kV cable. The voltage genrated by the circulating
current should be more than 130 V as per IEC standards. In
case of heavy circulating current the cable would get
heated up. You may do earthing of the cable only at one end
and leave it open at the other end. In case of a very long
cable with joints in between, mid point bonding is
suggested.
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
300m long and 30kw inductive loade 3phase supply how many size cable required
pls someone send me sample question papers along with the key.thanks in advance
What is MS-EXCELL?
How many types of losses occur in a transformer?
what about SAP/MRP regarding manufacturing of electric motors and all drives?
in single phase converter, the no.of scr's conducting during overlap a)1 b)2 c)3 d)4
What types of CMOS memories have you designed? What were their size? Speed? Configuration Process technology?
What tests should i carry over on a newly rewinded DC Generator with voltage rating of 38 volts and current rating of 350 amps, to certify that the machine is OK?
How to calculate that clean water supply in one Day from 150 KLD STP?
what is the excess air in furnace
Why are the laminations insulated from each other?
In Plumbing services What are accessories we consider for a bathroom?
what are symmetrical and non symmetrical components in electrical installation.
How PADO software increase the efficiency of power plant?
how to erect roof control panel?