Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How the Transformer oil testing is done & Why oil dielectric
goes LOW & what is solution for that ??

Answer Posted / saroj

TRF oil is tested in a glass pot where high voltage,KV is
applied between two electrodes and sparking at electrode to
be observed. For good oil , it comes about 40~60KV/mm .If
it comes lower then filteration is required. Those TRF
having tap changing is frequently required it is
recommended to do filteration in once in year.Also its
value goes low because of moisture ingress in oil .

Is This Answer Correct ?    5 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what happen if generator of micro hydro running at only a small percentage of its capacity, as a comparison, if the diesel generator that runs on only a fraction of its capacity there will be a wet stacking

1986


Whether should be the oil level in OCTC transfomer? It should be upto winding immersed completely or should be upto tap changer s/w? How it will affect the performance of the transformer. Rating may be 33KVA

1899


why we can stote dc? why we cant store ac?

2129


Working of microwave oven?

2305


The loads are connected with phase and ground then why current flow as the loads ?

2014


Dear Sir/Madam, I have one questions we have three steam turbines and one Gas turbine and our industry linked with the public network, we have protection system one of the protection is reverse power we can export just four MW only i would like to ask about how to calculate the reverse power. Thank you in advance best regards

2139


1.why should we connect the measuring instruments in l.v side in short circuit test of a transformer? 2.why the power factor is less in open circuit test of a transformer?

2123


how to calculate the earth fault current

2574


tell me about eletrical contractor

2002


Why are lt windings placed near the core?

1150


what is stper motor

2469


WHAT IS MEANT BY DERATING OF THYRISTOR?

3015


how can we determine size of a cable by knowing the kw or current rating of a load?how can we calculate the resistance box of a slip ring motor?

1832


How can we findout the maximum efficiancy of Transformer? At which load?

2137


how to differentiate a mpcb,mcb with a contactor? Explain their working operation

2287