How you calculating the current for a 2.5 Sqmm cable.
A 30 Hp 3 phase AC motor of power what size of cable is
used for this motor.
Answer Posted / shashank
deciding a cable has to consider following parameters also,
1. Safety factor of the cable (margin for starting current
say 1.25 in numerator side)
2. Deterioration / Degradation factor (say 0.8 in
denominator)
calculate the current of the motor by considering running
pf (power factor) say 0.8
as motor gives real power
e.g.
W = V * I Cos (phi)
30*746 = 415 * I * 0.8
I = 30 * 746 / (415*0.8)
I = 67.41 Amp,
Thus Current considered for cable (Icb) = 67.41*1.25/0.8
Icb = 105.3 Amps.
Select from the catalogue suitable copper cable for this
motor. Dont forget to consider the voltage drop per meter,
the total voltage drop shall not be more that + - 5%.
| Is This Answer Correct ? | 15 Yes | 9 No |
Post New Answer View All Answers
what things to be considered when designing UPS
what should be the acceptrd value of winding resistance for 2.5MVA transformer
How to calculate the time setting for star connection in star delta starter? For example 10KW 3PH Induction motor.
What are the advantages and disadvantages of open loop control system?
what is conductor constant of raccun conductor
if i get a drop in my 1st year and the i clear my 2nd year and 3rd year all clear and i dont have any back logs so can i be able to sit in campus selection??
What type of wiring series or parallel is used for conventional and addressable type FAS & why?
why ss stablity limit is more transient stablity limit?
why do we put a transformer on soak before loading it
Instrument connected to a single phase supply
What is a surge supressor why its is used in synchronous generators
hi there i am highly enthusiastic about discussing electrical concepts , and hence i wud lyk to invit al do intrested to join me at gtalk and hav a dscussun of the concepts , ad me as a freind . my email id is rakesh.2k99@gmail.com
types of central Air conditioner plant?
what is meaning of sympathetic tripping with respect to relays and give the values for current carrying capacities for copper and aluminium cables from 16sq mm to 500sq mm
What is the difference between grid and off- grid system??