in a electronic controller why we are using 250 ohm
resistance in input signal?is i/p is necessary in control
valve when we are using electronic controller give details?
Answer Posted / sam
The hardware electronic controller you are using has a 1-5
Volt input but the transmitter you use in the field, is a 4
to 20 mA transmitter. So in order for the hardware
controller to accept this input, you install a 250 Ohm
resistor on the controller's input which will convert it to
a 4 to 20mA input.
Weather you need a I/P converter on the control valve
depends on the positioner you will use. The hardware
electronic controller will give a 4 to 20mA signal to the
control valve, so if you want to use a full pneumatic
positioner on the valve, you need to install a I/P converter
and calibrate it for a 4 to 20mA input and a 20 to 100 Kpa
pressure output. You then need to calibrate the pneumatic
positioner for a 20 to 100 Kpa = 0 to 100% stroke.
If you want to use any other type of positioner a I/P will
not be necessary, since in electromechanical positioners the
I/P is already part of the positioner and obviously in SMART
positioners, the input to the positioner is 4 to 20 mA.
Good luck
| Is This Answer Correct ? | 24 Yes | 2 No |
Post New Answer View All Answers
What are different types of orifice plates?
What is limitation of the ht.of the displacer of a level trol?
what is the reset offset and control system in instrumentation
Sir, I am working as a Instrument Engineer in Grasim Industries. Can any body provide question answer for interview purpose
NSV type probe stands for
Why not come out analog output in ABB EL3020 when display show correct value
can any send me a forbes marshall dtron 316 manual
How to Calibrate Coriolis Flow transmitter in field
Why do you want to work here
please send me some question papers of HPCL aptitude test ?? please send it to bipinb.28@gmail.com ...
please send the drdo exam paper
what is the difference between magnetic flow meter and mass flowmeter
how to commission furnace ( water heater)
How to convert milliampares into flow??
what is the procedure of belt scale calibration?