How to calculate the Meter constant for the given Meter (by
using any formula)
Answer Posted / r.k.shah
Meter Constant for an Energy meter is the amount of KWH
used in its low voltage circuit for each revolution of the
induction disc. Here the explanations are given for a
typical industrial 3-Ph Energy Meter which is fed by a
suitable CT & PT.
To calculate the MC: If it is given that No. of Revolutions
per KWh then, MC is inverse of this no. For example, Let's
say for a certain Energy meter, No. of Rev./KWH is given as
4000, then MC = 1/4000.
If the No. of Rev. per KWH is given as a very small No.
like 0.06 or 0.16 etc. then it refers to KWH value in
primary circuit. That is, 1 KWH value passes in HV circuit
for given amount of Rev. To calculate MC in such cases,
invert such No. & then devide by CT & PT ratio.
Is This Answer Correct ? | 48 Yes | 31 No |
Post New Answer View All Answers
I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?
In what cases (circumstances)we should apply P controller, PD controller, PI controller & PID controller ?
What is the approximate value of stacking factor?
the winding of Generator and Motor is star or in delta ? and why
what is the voltages using in movie theaters??? why ??why not other??
What if the difference beween internal and exrteranal LBB?
what is effect of 5amp fuse on 2mva pry protection of transformer
how we provide neutral earth on synchronising panel as per electrical standards?
what is stper motor
how can i determine the gear ratio for a rack and pinion system if an electronic gate operated by an electric motor is to travel a distance of 5meters in 15 seconds.
for 100 HP Induction motor service factor is 1.2(SF) we placed a VFD at the motor side load is balance with 0.3 Amp's Phase to Phase but at incoming of VFD load is un-balance with 10 to 20 Amp's what will be cause of load un balance
why ss stablity limit is more transient stablity limit?
what is the difference between "Rotary bypass isolation switch and Normal bypass switch" pls share indepth techs?
What is rotating magnetic field?Discuss elaborately.
While testing LA mast,What are the parameter limits ?