how much Amp we can put in 1200kva generator?
Answer Posted / mohamed ali.m
Dear there are use the Formula
I= KVA X 1000/1.732 X 415
For Example
1200KVA
1200x1000/1.732x415= 1669.4 ( Full load Amps
= 1335.5 ( 80% Load Amps)
Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
How would you relate your key competencies to this position?
Distribution transformer we provided 2 separate earthing pit for Body and 2 separate earthing pit for neutral,we can not connect separate body earthing pit to other earthing pit but we do metal glanding in secondary side cable termination in both side, transformer and PCC panel (LT Panel), is this safe for transformer and other equipment?
Hi My dear all Friends, There is a question regarding HVAC Engineering and widely used in Power Projects. Question- What is the diffrence Between REF, SEF and Differential Protection....???? Where REF - Restricted Earth Fault SEF - Senstive Earth Fault.
block diagram of 2 ups system connected in parallel mode?
The power supplied to a 50mH inductor from a 120V, 60Hz source will be
The capacitive reactance of a capacitor of 1/(2(PI)) F at 10^3 H is
What are the advantages and disadvantages of the dc motors?
Explain about Leakage Test.
Determine the BTU size of an aircon for 20 sq metre room
what is the function of capacitor duty contactor in an capacitor panel???
What do you understand by avr?
why we use four type of phase angle difference between pimary & secondry winding of a transformer & where we use them?
Please tell me the formulaes while designing a substation for power Calculations in designing a 33 KV Substation?????
What happens if we run alternator on under frequency?
Write down the name of 2 lady Bir Pratin of Bangladesh