When a field input to plc is coming from 400 to 600 meters
and the input is in 24 V DC? So signal cable of which cross
section i should select for proper signal to plc?
Answer Posted / janes
It is all depends on the Load of the Field Instrument.
After Getting the load apply the Voltahe Drop Formula.
Also the input is 24VDC but define the Amp. is it 20A/ 10A.
that is 24Vdc 10A.
For 24VDC 10A Power supply and the Field Instrument is SOV
with 18 Watts, and the Distance is 600 meter then use the 2
Core 2.5 Sqmm Cable as per below Formula.
% Voltage Drop = Length X Current X R Cos0 + X sign0 /
Number of run X Voltage X 10.
| Is This Answer Correct ? | 2 Yes | 5 No |
Post New Answer View All Answers
What is the purpose of bypass valve across AS valve.
what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?
how to measure oxygen which methods are using?
send me last 5 years questions asked in rrb chennai, for section engineer
How can a d.p. Transmitter be calibrated?
I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?
what is performance test.need defination
Meaning of the following a. IOP- Manimum; b. IOP- Maximu,;
What are the interlocks we have to check during the start up of LP/HP compressor?
what is RTV function in in process control?
Why even multiple power supplu r used in instrumentation system?
Speedtronic system .
I am having a Phoenix digital to modbus converter. The o/p of the same is connected to flow computer FB407. But the digital signals are updated only after one minute in the flow computer. what may be the cause of delay in communication? Flow computer is having a scanning period of less than 1 sec.
can anyone tel the syllabus or previous year question paper for BHAVINI(EIE)2014.
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks