If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / munish saini
KW=KVA*PF
PF=.8
KW=375
KVA=KW/PF,=375/.8=468.75KVA
20 Percent required more as eppiciency Factor
so required dg should be=562.5 KVA
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
If an electrical component has a positive temperature coefficient, how come such components have high power losses due to heat if current decreases when resistance increases? assuming power given by I^2*R whereby the Resistance is infinite.
Dear sirs, pls check this 4-20ma to RS485 module datasheet,pls guve me some suggestions. http://www.szsunyuan.com/sy/pro_more.asp?Productid=539 Thanks. E-mail:yunianjiang99@gmail.com
Why front mounted CT polarities are always towards breaker?
can i use ups power as a raw power for another ups
what is the meaning of WYE and DELTA in Electric meter?
along with technical test papers
If I bring a basic electric meter from the States and hook it up in Costa Rica in a development that has only one transformer for the 50 homes, will it still be accurate regarding the usage of kilowatt hours?
What is the formula to calculate the rating of a three phase air circuit breaker
75 kw motor take 45 amp in no load delta in star 10 amp but in load it will take 160 amp but IR velue of winding above 500 at 1kw ph to earth and ph to ph. what problem it should be?
Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.
What will be electrical cost per sqft for IT building (basebuild and fitout)and for residential township?
From past few months I am getting lagging pf even though sufficient capacitors used in circuit. Where is the problem pls answer
Mention the methods for starting an induction motor?
why 3 phase is converted into 2 phase using electronics circuit why not 2 phases are diresctly putted from the 3 phase transformer??
What is the difference between a 3 winding and 2 winding Potential Transformer