Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the function of anti-pumping in circuit breaker?

Answer Posted / kayode j.

The anti-pumping relay is a device in circuit-breaker whose
function is to prevent multiple breaker closures. For
instance, if the operator gives the closing command to the
breaker by pressing the close button and the breaker
closes. However, a fault in the system causes the breaker
to trip. Since the close command is still in the pressed
condition, there is a chance of the breaker closing again
and being tripped by the relay multiple times. This can
damage the closing mechanism of the breaker. The anti-
pumping relay prevents this by ensuring that the breaker
closes only once for one close command from the control
panel.

Is This Answer Correct ?    249 Yes 12 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the difference between a verilog task and verilog function?

1388


What is corkscrew rule?

1200


please send the IS strandard for electrical to sakthi_murugan86@yahoo.co.in

2312


When we giving the 3 phase supply to ups system how to coming netural?

2159


What is a compensator?

1139


What are the section criteria for cables. Now everywhere XLPE power cable is used or PVC is also used?.

1711


What are the site acceptance tests for power cables, DG Sets, LT panels & 30kVA UPS ?

2436


What is mean by spike arrester(Voltage Operated)

2111


HOW TO CALCULATE THE HEAT AND LOAD OF LT-SUBSTATION WHICH CONTAINS 2*1MVA TRANSFORMERS,LT-SWITCH BOARD,MLDB,ACB,BUSBAR,ETC,......?

2157


Explain the advantages and disadvantages of thermal power plant?

1141


can mini-curcuit supply MIL-tested transformer !

2187


can i use ups power as a raw power for another ups

2030


can u describe the method used for protection of transmission line.

2258


What is the percentage loss for aluminium wire for HT line more than 11KVa

2177


What is the vector group of a transformer,how can it be found out?

2099