Why in medium voltage system(3.3kv to 33kv, neutral is
earthed with either resistance, reactance or neutral
grounding resistance?
Answer Posted / avdheshlakhera
You need to limit earth fault current in medium voltage
system if rotating machines are connected to the system.By
adding NGR E/F current is limited hence during earth fault
in motors or in generators there will be less core damages.
This will reduce repairing cost of machines (Repairing of
core damages are very costly in large machines). Only thing
you need to do with resistance grounding system is to
select sensetive relays and set them correctly.
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
Different types of relay fault which phase sequence??
how to deside the capacity of chock for drive?
i have done diploma and btech in EE and live in Chandigarh so kindly help me how can i make my competency certificate in my area.
In MEP Services what are parts of STP and what are there function?
Why PS class CT is always preferred for Differential protection?
how invertor convert the dc into ac give brif detail
use of choke in APFC panels
specify the inbuilt protections in DG
area control error
i need some project topics along with circuit diagram in the electrical adnd electronics engg and also give ome website regarding projects.my mail id is thenmozhi2k7@gmail.com .please help me.
What is the BS(British Standard)code for 11kv motor
in the case of 6.6kv motor starter combination contain fuses on it VCB. but in 11KV motor starter combination Fuses are not using in it's VCB why?
Is there any rule to select the voltage of motor based on KW rating? What is the rating above which lt motor becomes the HT motor?.
We have 110Vac ,10A ac supply which is converted into 110VDC & How much DC current? which factor is reqired for dc current calulation?
why do we use 25kv supply for traction purpose?