Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why in medium voltage system(3.3kv to 33kv, neutral is
earthed with either resistance, reactance or neutral
grounding resistance?

Answer Posted / avdheshlakhera

You need to limit earth fault current in medium voltage
system if rotating machines are connected to the system.By
adding NGR E/F current is limited hence during earth fault
in motors or in generators there will be less core damages.
This will reduce repairing cost of machines (Repairing of
core damages are very costly in large machines). Only thing
you need to do with resistance grounding system is to
select sensetive relays and set them correctly.

Is This Answer Correct ?    5 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Earth bits close or open. Which is correct

1871


i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.

1873


Why is a synchronous motor always star connected??

2537


as a electrical student why should i hire you?

2437


dear all i am kumara now current working in electrical designing of control and relay panel i want learn some substaion design then any book are available. pls mention name and authour

1895


if we install two earth pits with a clear space of 5m without any interconnection,by checking the digital multimeter will it show continuity between earth pits? If so what would be the approx. value

1867


How to calculate earth wire load by formula

2512


i need the details about bhel exam.how to apply for that.please send to my email-id.thenmozhi2k7@gmail.com

1969


State nyquist stability criterion.

1108


Readings of ER300P Trivector meter

6363


is IS says that neutral should be brought to switch box. and this one is a recomended practice

1811


Air refrigeration cycle works on the

1035


What the main causes of transient interruptions on Over-Head Distribution Lines?

2050


hi frnz,can somebody give me any project work? i am a 2nd year student & interested in practical works...plz give me some projects

1931


HOW TO CALCULATE HV CABLE SIZING?

3139