How the Transformer oil testing is done & Why oil dielectric
goes LOW & what is solution for that ??
Answer Posted / pillay
The sample oil to be tested for dielectric test is collected
and put into the tester and the average of 6 tests is
taken.The minimum withold voltage is as per local regulations.
causes of low dielectric results are usually exposure of the
insulating oil to moisture through the breather or there is an
exposed opening, poor quality oil being used. high acidic
content.The insulating oil should be replaced or dehydrated.
breathers silica gels should be maintained good all the time
and check for any leaks or any exposure to atmosphere must be
rectified.
| Is This Answer Correct ? | 15 Yes | 1 No |
Post New Answer View All Answers
details of oil cell size of Breakdown voltage test of tranformer oil details as per Standardswith mushroom electrodes?
What is cross over distortion? How it can be eliminated?
Dear sir my name Ankit i m Diploma holder present working in Welspun Corp ltd Anjar as Asst.engg (salary 14400/month ctc) i Would like to change my company also i have selected in ford India pvt ltd Sanand as trainee Tech with salary 12000/month so please suggest me for changing my job hope for *ve response
what is the disadvantages of common earthing for AC and DC equipment? (i am talking about inverter control room and inverter duty transformer earthing is common...?)
one split ac how can told of this ac which Tr tell me us
Basic motor transformer generator
what is the difference between switchgear and circuit breakers and is there any difference between outdoor and indoor switchgear and circuit breakers , and how would you differentiate between switch yard and substation and grid station . thanks
the winding of Generator and Motor is star or in delta ? and why
You are of electrical field and you are going for software? Why
Single line diagram for dbb (double bus bar)system.
Why using synchronising methed in DG's sets?
how did the testing of protection relays done through current injection
WHAT IS THE PARTIAL DISCHARGE TEST?
What is the maximum No. of out going mccbs permitted from an LV distribution paqnel? What is the ampere relation between incomer and out going switch gears/mccbs?
For high frequency application we use which transformer?