Assume a condition such that two motors of rating
6.6kv,415v are connected to blower,so tell me which motor
draw large current give appropriate reason?
Answer Posted / pillay
The current drawn depends on the power consumed by the motor
and the operating voltage.
KW =1.72 X VL X IL X PF
Now assuming both the motors are loaded at 100 kw each OF PF
0.8 than the 6.6kv motors current consumption will be
100000KW /1.72 X 6600 X 0.8 =11 AMPS
If 415 volts is used than
100000 / 1.72 x 415 x 0.8 = 175 AMPS.
Is This Answer Correct ? | 17 Yes | 1 No |
Post New Answer View All Answers
percetans
What is the meaning of loop in transformer
how to calculate insulation level of transformer?
what the Microsoft .NET framework is?
how we sesign the transformer give some specifion regarding design of transformers
Is MEN and RCD related to each other ?? IF yes then how??
what are the components in electrical control panel (for example: 415V, 3-ph, panel to operate utility and 3-ph DG set).
Explain what is electric traction? Explain few advantages of electric traction system?
The power supplied to a 50mH inductor from a 120V, 60Hz source will be
Why let through energy not considered for ACB breaker while cable sizing?
what is the difference between ac motor and dc generator
how will calculate the safe starting current of 3-phase squirrel cage induction motor?
If we are given a 10 amp cable type and asked to calculate the number of cores used and the thickness of the cable, how do we do it?? please help...urgent!! i hope the question is clear enough!!
Showing results for capital, machinery, stock,wages, carriage in words, salaries, factory rent, repairs, fuel and power, buildings, debtors, sales, purchases, creditors, return outwords, return inwords, drawings, discount allowed, discount receivable, office expenses, bills payable, bills receivable, cash in hand, cash at bank, office rent comes under debit or credit
why the making current is more than then the breaking current and if its true then its about a controling circuit or breaker power contact points