in 50 mw generator if field is open in full load running
condition what happen and for protection which relay used?
Answer Posted / a1
I is depend on type of operation-
1) If parrallel with grid/Other generator, than it will
draw reactive power from the Grid/Generator and give active
power to the load. It will work as a Induction Generator.
Reactive power of connected circuit will unbalance.
2) If Generator is running island mode(without any other
source), than terminal voltage of genertor will start to
decrease and current will start to increase. Winding temp.
of Generator and drives will increase.
Under excitation relay provide for this.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
Discuss about gear cutting machines.
briefly explain the main blocks found in a microprocessor based system
Can anyone explain me about the RLC based Impulse high voltage generator and how to and operation of Series resonant High voltage reactor...?
How to design a Unit auxiliary transformer for a power house having a unit of 65 MW and Generating voltage of 11 KV and Secondary voltage of 433V
How to justify this statement ??? "Capacitors in series provide less capacitance but higher voltage breakdown rating for the combination"
how to test power transformer.YNd11
What are the advantages of a three-phase system over a single-phase system?
Why efficiency in thermal power plant is low?
Pl.brief me any electrical major fault you have rectified.
how to calculation increase power factor for single phase
What is expention fastener (Fan)
what is data block in plc ? How the values of data block are written and read by hmi ? what is the difference between function and function block ?
Actuality I have at home electrical panel with 220v 50hz, and I want to converter from there to 110v 60hz, to wiring on the half of my house. Also I like to keep another half of my house with the original 220v 50hz. What is the best and safety way to do?
sometime battery charged and then automatically charged when rectifier ON conition, is there any chances please clarify the same.
It is desired to flood light the front of a building 42 meters wide and 16 meters hig.Projectors of 30 degree beam spread and 1000 watt lamps giving 20 lumen/watt are availabl.If the desired level of illumination is 75 lumen/m and show a suitable scheme.Assume the cofficient of utilization, deprecitation factor and waste light factor are 0.4, 13 and 1.2 respectively.