If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / srinivas
if the connected load of plant is 375kw. but any time all
the load may not be there. if peak load may be 300kw at any
instant so KVA rating of DG=KW/cos(phi) so you can take
300/0.9= 333.33 so you can take 350KVA Dg you can go for.
| Is This Answer Correct ? | 2 Yes | 3 No |
Post New Answer View All Answers
what are the applications of TIG welding
PLEASE SEND THE PREVIOUS YEARS QUESTION PAPERS OF RRB JUNIOR ENGINEER-ELECTRICAL
Explain what is use of lockout relay in ht voltage?
how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar
What is the exact minimum vale of voltage between an earth and netural which can damage or can do malfunction of the electronic equipments ? If this is mentioned in any book, pl.give reference.
what happen if generator of micro hydro running at only a small percentage of its capacity, as a comparison, if the diesel generator that runs on only a fraction of its capacity there will be a wet stacking
Why do we use copper cable for HT Supply and why not Aluminium?
what is the preventive maintence for ht panels and busbars and vcb abd acb's.
how many Classification of fire extinguisher
Why the cores of large transformers build up of circular cross section?
what is die electric strnth of transformer ?
how the synchronizing is obtained at bus couplers in grid substation? (because there we cannot change the frequency in one of transmission lines like in generator synchronization)
How to connect the chemical earthing and complete process tell me plz
Name one of major transformer company in KSA ?
I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?