11KW Delta motor is taking about 44Amps in star and goes
upto 70Amps in delta and trips OFF. The rated current is
26Amps. Application is for the blower. The motor takes ( no
load without coupling impller ) only 2.5A and 5Amps in star
& delta starter test.Need to know why its taking high
current.
Answer Posted / gunasekaran
u r not explain proberly it is due to inrust current for
star phase voltage=VL/sqrt3
for delta phase voltage=line voltage so it is taking more
current than star.normally at stating motor taking 5to 6
six times of the full load current i think nothing wrong u
can incress the relay setting and then start the motor
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
what is the ground fault relay,which purpose it will be use,clearly tell me plz
11 kg trivevter meter has rating of -/5amps. And pt ratio11000/110v and is connected with 11kv ct/pt unit of cr ratio 75/5amps. And pt ratio of 11000/110v while checking accuracy of meter with HT Accuchek meter what value of PT ratio and CT ratio to be filled in Accuchek meter
what are problems caused by the pdu in rack server
Explain what is electric traction?
What is the significance of integral controller and derivative controller in a pid controller?
What are linear and non-linear systems?
The sodium vapor lamp is not glows when it is connected a distance of 5 meters above from gearbox, why ?
I have one ct of ratio 3000-2000/1 Amp its knee point voltage mentioned on name plate is 500-333/30mA-50mA at Vk/2. in secondary box there is three terminal named 1S1, 1S2, 1S3 then on which terminal obtained the knee point voltage ie 1S1-1S2 OR 1S1-1S3 & also specify the knee point voltage for the ratio 3000 from name plate.
State kirchoff current law?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
Why it is possible to use PWM with a STATCOM and not with a conventional TCR based SVC
How many types oil using in transformer ? How many letars using in transformer..?
Differentiate between ideal and non-ideal voltage sources?
design a LV scheme for a 15 storied building?
How we calculate the current carrying capacity of H.T. cabel?