Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What the capacitor Current formula?, For 1 KVAr how amps
its required? for using the KVAr for boosting the PF Design
Calculation.( Eg: for 30 KVAr required how many KW?)

Answer Posted / arnie

For correcting PF KVAr is introduced, thus formula

pf=cos A is significant

there you should have a desired PF. If for example you need
a power factor of .90 to maintain for a 30kVAR the watts
that would come will be:

A=arccos .90
A= 25.84

WATTs= KVAR/tan 25.84

= 62500 watts approx.

remember that for PF correnction it is the KVAR that is in
need of computation and not the watts so the question would
rather be, how much capacitor kVAR you need to correct the
power factor.

Is This Answer Correct ?    40 Yes 24 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to calculate mf when meter and cTPT detail are given

1799


How does a battary stores charge in it? please explain in simple manner and in detail.thanks

1922


What is Plank's Law?

1093


What information we need to prepare relay coordination chart

2264


How many turns are there in primary winding? (In Transformer)

1641


What do you mean by the zone of protection?

1033


What are the different types of transformers?

1088


What is the real function of reverse power relay in generator panel while syncronising?

2116


Explain how you decide what size of electrical wire do you need?

1065


how to decide the panel size like MDB ,SMDB PANEL SIZES

7293


What is highest size of HT motor like 11 kv or 33 kv,and how to make it 750 rpm.i think the size will be very big.any idea ? pl. reply..

1874


what is the transformer rush current?

2024


What is effect of harmonic current (Draw by VFD) on power system/ electrical Equipments ?

2008


kindly send me 11KV MV motor differential protection procedure by primary injection method.

1375


reason of diode failure in alternator

1781