WHICH INSTRUMENT USED TO CALIBRATE CONTROL VALVE?
Answer Posted / chek mohidein
For the calibration of a control valve a loop calibrator or
a pressure calibrator can be used between 3-15psi.Check the
valve position for 3psi which is to be 0 for a NC type
valves.In such manner check the valve positon for various
ranges(6psi,9psi,12psi & 15psi).the valve positon shoul be
0 for 3psi and 50% for 9 psi and completely opened for
15psi.
The same procedure is applicable for NO type valves.The
valve is open for 3 psi and completely closed for 15psi.
Any errors occured may be rectified by Zero span adjustment.
| Is This Answer Correct ? | 50 Yes | 3 No |
Post New Answer View All Answers
Any body have know try work calculation ???
how can use ram
If i have 4 Allen Bradely make RS logix 5000 PLC and for viewing that we are using 4 RS view SCADA for 4 different packages. Now, I will want to view two packages on only one SCADA. Then how i will do it?
sir, give me placement papers and interview quistion of birla group company of copper.
How to Calibrate Ultrasonic Level Transmitter in field
How is PH sensor works ?
Do you have reference list?
How addressable fire systems work? Pl. send details with architect.(Loop), also send details regarding Gas system. Pl. help me.Thanks
What is three element in drum level?
Who to difference between analog in & analog out in dcs?
How digital input and digital output 's are working in dcs
What is the difference between conductive lined pipe and conductive unlined pipe? Why do we see that?
In turbine what does term CDP, NH, HSSOC means.
Hi Friends , i need one urgent help , i am preparing for M.tech entrance examination , i need some obejective questions related to instrumentation field. where can i get those ? can anyone help me pls ?
What are the error values can accepted in flow transmitter calibration?could u give any formula for this?