If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / sukhvinder
connected load=375kw
kva=kw/cos phi
kva=375kw/.8
=468.75
extra load= 20% (assume) i.e 468*20%= 93.6
total 468.75+93.6=543.68 kva say 550kva
eff. 375/550*pf (0.8)*100=85%.
| Is This Answer Correct ? | 25 Yes | 2 No |
Post New Answer View All Answers
Can anyone provide with a SLD for HT panel installation for a 33KV line and distribution end has three 1.5MV transformers. Is it suitable to use OCB or VCB and also provide me the suitable rating and its connection diagram.
we use 400/5A ct and 35/roor3KV,/0.1/root3KV,0.1/root3KV pt ratio. What is the multiple factor of this meter.
IF alternator SCR value will be high means what happen in alternator efficency at operating power factor of 0.8
In three pin plug 6 amp. 220V ac rating. Why earth pin diameter is higher than other two pin? What its purpose ?
Load transfer in 11kv double busbar switchgear - operation.
bsec exam syllabus (mis)
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
please give me all the Alarm .Trip ,Safety Relays & Conditions of Diesel-generators mail me on ashokbabunhce@gmail.com
what is droop control?
What is an automatic controller?
Explain what cmos is and its benefits?
Why temperature rise is conducted in bus bars and isolators?
I have motor of 3 H.P. How i found the rating of capacitor use in it in single phase motor..???
any idea abt REVERSE METERING concept.........?
Differentiate between induced emf and self inductance?