Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate circuit breaker capacity

Answer Posted / hari

If u have the fault mva and the voltage level at which the
CB is to be installed then :
Normal current would be the continuous current flowing in
the line ( u can take the next higher value from standard
values to take care of over current)
Breaking capacity would be tha fault MVA.
Rated symmetrical breaking current in kA would be Fault
MVA*1000/(1.732x Voltage in kV)
Rated making ct would be peak value of symmetrical breaking
current i.e 2.55 times breaking current
Short time rating would be rated symm breaking ct for 3 secs

Is This Answer Correct ?    95 Yes 17 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Define the term Capacitance and Inductance?

1166


what is the eight bit unit?

2504


what's the simultenous maximum demand (SMD)..what the diffrent MD and SMD?

2619


what is metering cum synchronizing panel and how it is used?

4708


What happens if the negative to earth voltage is greater than positive to earth voltage in the battery of substation?

1614


I WANT YHE TECHNICAL AND ELECTRICAL SPECIFICATIONS OF 2x4MW 11KV 2x10MW 11KV 2x25MW 11KV 2x100MW 11KV HYDEL POWER PLANT i.e PROTECTION SYSTEM,MONITORING,CONTROL SYSTEM,GENERATION,SYNCHRONISATION,METERING PLEASE SEND THE DETAILS TO MY MAIL ID SPRAVEEN_222@YAHOO.CO.IN

2145


how to find the voltage's of a transmission line plzz help with pictures i am not able to understand

1425


where is the need for short circuit test for 3 see is required and why? can you explain in brief with application

2009


I am using submission of two ct in one and half scheme for 67/67N protection. Both CTs star point is grounded separately near ct box.Will two point ground give wrong tripping to 67/67N during fault or no matter.

2156


how to work droop ct in generating station

2759


Explain what are inter-poles and why they are required in a dc machine.

1141


what's the exact magnitude of current, flows through Neutral?

2007


WHAT IS THE WORKING PRINCIPLE OF A GENERATER.how is a GTG (Gas TURBANE Generater) working.plz explane

2581


what is mean by NPS (Negative phase sequence)fault? what is the difference between EFR & OCR faults?

2420


Earth is a conductor or load?then ammeter connect to 3- phase supply,it shows the measurents or not?

2142