how to check thermocouple ,its working or not?

Answer Posted / v.r.m.kiran

check physicall condition.
Then check the resistance of therocouple.
if it is open theremocouple is dead.
if it showing some ohms nearer to Zero. Then it is ok.
Then heat the thermocouple check the mv & verify with the
standard chart.

Is This Answer Correct ?    61 Yes 7 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

WHAT ARE THE INSTRUMENTAL DIAGRAMSOF VALVES?

1676


model question paper of instrumentation for Jindal GET 2010.plz reply sudhanshukumar08@yahoo.com

1898


Explain the use of hair spring in the pressure gauge.

662


I will attend an interview with GasGas company for a position of Instrument Technician ( Offshore )in next month can anyone tell me what questions they will ask. Thanks in advance.

1644


If fire would be inside the plant which fire detector is to detected the fire.

1071






What is modbus?

669


POSSITIVE PULSE IS APPLIED TO AN INVERTER INPUT.THE TIME FROM THE LEADING EDGE OF THE INPUT TO THE LEADING EDGE OF THE OUTPUT IS 10 ns. THE TIME FROM THE TRAILING EDGE OF THE INPUT TO THE TRYLING EDGE OF THE OUTPUT IS 8 ns. WHAT ARE THE VALUES OF tPLH and tPHL?

1757


How to calibrate H2s Dectector

1189


selection criteria of control valve? and selection criteria of actuator explain in brief?

3652


Why the ammonia and Nitric Acid level indicators is with millimeter ? and What is the conversion form millimeters that level indicator indicate to weight ?

1211


 why Fahrenheit unit of moistur analyzer transmitter

1787


what is IEC code in cables & how to selecting cables?

1290


how to calculate control valve bonnet size?? or how to select its material?

1954


In turbine what does term CDP, NH, HSSOC means.

1341


Can anybody please let me know Orifice plate sizing calculation formula and step by step procedure

1510