three phase 180kva diesel generator can take how much load
in amp and what is formula to get this?
Answer Posted / santosh jagale.
Generator rating is 180KVA.
Actually all electrical data is made avialable on genrator
name plate by manufacturer.
If you consider the PF is 0.8 Lag.
Then KW=KVA*PF
i.e. KW=180*0.8
=144 KW
P(KW)= 1.732*V*I*PF
Then,
144=1.732*415*I*0.8
I= (144/1.732*415*0.8)*1000
I= 250.42 Amps.
This is the full load current of generator with 0.8 PF &
415V.
In case of DG sets the generator O/P power is restricted by
power of driving engine, beyond that limit you can,t load
the particular generator. You can put upto 125% of to
genrator but not for too long period.
| Is This Answer Correct ? | 52 Yes | 4 No |
Post New Answer View All Answers
What is touch potential and step potential?
Why PT voltages are measured with respect to ground? What do u mean by voltage or current polarized.
What is use of starter and choke in tube light
What will be in Mahagenco Trade Test Exam? I want to know the same.
Why do we pefer VCB over OCB?What are the advantages of VCB over OCB?
how we calculate the withstansing current capacity of wires&cables?
why various test are performed on electrical panels & power cables before commissioning on site & what are these test???
can we choose current transformer secondary, to calculate residual flux in a power transformer, so as its saturation is close to the saturation level of power transformer?
HOW TO CALCULATE S/C,O/C,E/F OF ACB.
Transformer how to maintaince a check b check c check d check
what is a bus riser in power system and why it is used
How many VSC based HVDC are there in India and the world
State thevenin’s theorem?
What is A check, B check, C Check & D check for a diesel Generat
What are n circles?